2 adjustment of the modbus interface, 2 adjustment of the modbus inter- face – VEGA VEGACOM 557 Modbus protocol User Manual

Page 21

background image

VEGACOM 557 Modbus

21

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

Multiple plug

Basic board

Bottom view of VEGACOM 557

DIL switch
basic board

Front
plate

DIL switch blocks

additional board

Additional
board

2 1

1

2 3

Hook switches
additional
board

Adjustment possibilities for DIL switch block 1 on the
additional board

Switch adjustments on VEGACOM 557

3.2 Adjustment of the Modbus inter-

face

Three 8-pole DIL switch blocks as well as two
hook switches for configuration of the Mod-
bus interface to the DCS or the PLC are lo-
cated on the additional board.

The following adjustments for the Modbus are
made via these DIL-switch blocks:

Switch 1
- selection of the interface type
- activation of the bus termination
- selection of the protocol

Switch 2
- selection of the baud rate
- number of data bits
- mode for parity bit
- protocol mode (Modbus)
- definition of the measured value image

Switch 3
- Modbus address of VEGACOM 557

Note:

When holding VEGACOM 557 for adjustment
of the DIL-switches 1 to 3, the following
switch representation can directly imple-
mented.

Note:

When selecting the interfaces TTY and
RS 232, the hooks switches must also be set
to the respective position.

Activation of the bus termination on RS 485 is
necessary if VEGACOM 557 is the last par-
ticipant on the Modbus. General rule: The first
and the last bus participant must be oper-
ated with the bus termination activated.

When selecting interface RS 422, the bus
terminator must as a rule be activated on
VEGACOM 557.

DIL switch block 1
(additional board)

Selection of the interface type

Bus termination for RS 485/422

Protocol selection

TTY

RS 422, RS 485

RS 232

On

Off

Modbus
(RTU and ASCII)

Factory setting

1

2

3

4

5

6

7

8

ON