Field control wiring, Fig. 4 – field control wiring, Sensor – York ECO R-22 User Manual

Page 63: Space sensor 7 wire thermostat

background image

FORM 100.50-EG3 (802)

63

YORK INTERNATIONAL

* Use Shielded Wire

* Use Shielded Wire

* Use Shielded Wire

3. Maximum power available from the 24 VAC

1. Wiring shown indicates typical wiring.

Closed = Smoke Purge

Closed = Shutdown

Open = Unoccupied

Closed = Occupied
O

1.5K Adjust

Signal

cause equipment damage.

power source external of the unit may

i

d

sourced from the unit. Use of another

Note, 24VAC switch voltage must be

d f

h

i

U

f

h

Relay Output

VAV Heat

Smoke Purge Input

Shutdown Input

Unoccupied Input

Occupied /

to open full.

command the VAV boxes

output shall be used to

d h VAV b

Note: VAV Heat Relay

h ll b

d

Common

24 VAC Signal

Open = Normal

Potentiometer

Common

0-5V Output

Sensor

Common

Signal

CO

Open = Normal

4. Use shielded wire where shown.

terminal is 40VA.

2. All wiring is Class 2, low voltage.

Wiring Notes:

Common

Signal

Space Sensor

7 Wire Thermostat

G (Fan)

Y2 (Cool Stage 2)

Y1 (Cool Stage 1)

R (24VAC)

COMMON

RTD Sensor

1K Nickel

IA

Q

+

CO

M

SS

A+

3

1

2

4 5

S

HIELD

7

9

S

HIELD

13

15

Y1

CO

M

HR

S

MK

R

(24 VAC)

S

D

OCC

18

17

19 20 21

2

W1

W1 (Heat Stage 1)
W2 (Heat Stage 2)

Field Control Wiring

FIG. 4 – FIELD CONTROL WIRING