beautypg.com

Supply fan data, Continued) – York ECO R-22 User Manual

Page 38

background image

YORK INTERNATIONAL

38

Supply Fan Data

(continued)

TABLE 15 – 70 THROUGH 85 TON SUPPLY FAN DATA

TOTAL STATIC PRESSURE (Pascals of water column)

m3/hr

245

373

498

622

747

STD. AIR

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

27184

4.2

397

5.5

467

30582

5.3

411

6.7

478

8.2

538

9.8

596

11.4

646

33980

6.4

425

7.9

488

9.5

547

11.2

599

13.0

648

37378

7.8

441

9.6

503

11.3

559

14.0

610

14.9

658

40776

9.3

457

11.2

517

14.0

570

16.0

620

16.9

667

44174

11.3

475

13.3

533

15.4

585

17.4

633

19.5

678

45873

12.1

483

14.4

540

16.5

592

18.6

639

2.8

684

47572

13.8

492

15.4

548

17.7

599

19.8

645

22.4

689

50970

15.5

511

18.2

565

2.5

615

22.8

660

25.1

703

54368

17.9

530

2.6

582

23.3

631

25.8

674

28.2

716

TABLE 15 – 70 THROUGH 85 TON SUPPLY FAN DATA (CONT’D)

TOTAL STATIC PRESSURE (Pascals of water column)

m3/hr

871

995

1120

1244

1369

STD. AIR

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

27184

30582

33980

14.7

696

37378

16.8

704

18.6

745

2.9

791

40776

18.9

711

3.0

752

23.7

792

25.3

832

27.9

877

44174

21.6

721

23.8

762

26.0

801

28.3

840

3.8

879

45873

22.9

726

25.1

767

27.4

806

29.7

843

32.2

880

47572

24.3

731

26.5

772

28.8

810

31.2

847

33.7

881

50970

27.5

743.5

29.9

783

32.3

820

34.8

857

37.3

891

54368

3.8

756

33.3

794

35.8

830