1°c air on condenser coil, 5°c air on condenser coil – York ECO R-22 User Manual
Page 31
FORM 100.50-EG3 (802)
31
YORK INTERNATIONAL
TABLE 9 – COOLING PERFORMANCE DATA* – 85 TON MODEL
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
257
196
256
172
255
153
254
133
252
114
–
–
27184
19
241
223
237
204
236
185
236
166
234
148
233
129
17
239
239
233
225
232
223
219
196
217
181
216
162
22
264
209
263
181
262
161
261
140
259
118
–
–
30582
19
248
239
244
217
242
196
242
175
241
155
240
135
17
249
249
244
242
239
238
226
209
223
192
222
170
22
275
233
273
199
272
175
270
151
268
126
–
–
37378
19
264
269
254
242
253
218
252
192
250
168
249
144
17
269
269
261
264
256
263
240
237
233
212
231
186
22
284
258
281
218
280
190
278
161
276
134
–
–
45307
19
286
299
263
268
262
241
260
210
258
182
257
154
17
291
291
272
276
279
287
256
268
242
234
239
203
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
246
191
246
168
245
149
244
129
242
110
–
–
27184
19
231
219
227
199
226
181
226
162
225
144
224
124
17
230
230
224
217
224
216
210
191
208
177
207
157
22
253
204
252
177
251
156
250
135
248
114
–
–
30582
19
238
234
234
212
232
192
232
171
231
151
230
130
17
240
240
235
233
231
230
216
204
214
187
213
165
22
263
227
262
195
261
170
259
146
257
122
–
–
37378
19
254
263
244
237
242
212
242
187
240
164
239
140
17
258
258
251
254
247
254
230
231
223
206
222
181
22
272
252
270
213
269
185
267
156
264
130
–
–
45307
19
275
287
252
263
251
235
249
204
247
176
246
149
17
280
280
262
265
270
277
245
256
232
228
229
197