Cooling performance data – 50 ton model, Cooling performance data, 50 ton model – York ECO R-22 User Manual
Page 16: 35°c air on condenser coil, 4°c air on condenser coil

YORK INTERNATIONAL
16
Cooling Performance Data –
50 Ton Model
TABLE 2 – COOLING PERFORMANCE DATA* – 50 TON MODEL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
35°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
29.4°C AIR ON CONDENSER COIL
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
189
141
188
125
187
111
186
99
186
86
–
–
22653
19
179
162
175
148
173
134
173
121
171
108
170
96
17
179
179
170
172
164
169
160
156
156
143
157
125
22
190
143
189
126
188
112
187
100
187
86
–
–
25485
19
180
165
175
150
173
135
173
122
172
109
171
97
17
180
180
172
174
166
168
161
153
157
140
158
122
22
191
146
190
128
189
113
188
101
187
87
–
–
29733
19
181
168
176
152
175
138
174
124
173
110
172
97
17
181
181
173
176
167
164
162
150
158
137
159
119
22
196
156
193
134
193
119
192
104
191
89
–
–
31148
19
186
184
181
163
180
147
179
130
178
115
176
100
17
189
189
181
183
175
179
167
158
165
144
164
126
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
182
138
181
121
180
108
180
96
179
83
22653
19
173
159
170
146
167
131
167
118
165
107
164
93
17
173
173
166
167
159
150
156
140
153
128
153
114
22
183
140
182
123
181
109
180
97
180
84
–
–
25485
19
174
162
171
148
168
133
168
119
166
107
165
94
17
175
175
167
169
160
152
157
142
154
130
154
115
22
184
143
183
124
182
110
181
97
180
84
–
–
29733
19
175
165
171
150
169
135
169
120
167
107
166
94
17
177
177
169
171
162
155
158
144
155
132
155
117
22
188
153
187
132
186
116
185
101
184
87
–
–
31148
19
182
182
175
159
174
144
173
128
171
109
170
97
17
184
184
176
178
169
169
162
153
159
140
159
125