ELECTRICAL SERVICE SIZING

In order to use the electrical service required for the cool-
ing only eco

2

rooftop, use the appropriate calculations

listed below from U.L. 1995. Based on the configuration
of the rooftop, the calculations will yield different MCA
(minimum circuit ampacity), and MOP (maximum
overcurrent protection).

Using the following load definitions and calculations,
determine the correct electrical sizing for your unit. All
concurrent load conditions must be considered in the
calculations, and you must use the highest value for
any combination of loads.

Load Definitions:

LOAD1 is the current of the largest motor – com-

pressor or fan motor.

LOAD2 is the sum of the remaining motor currents

that may run concurrently with LOAD1.

LOAD3 is the current of the electric heaters – zero

for cooling only units.

LOAD4 is the sum of any remaining currents greater

than or equal to 1.0 amp.

Use the following calculations to determine MCA
and MOP for units supplied with a single-point power
connection:

MCA = (1.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4

MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4

If the MOP does not equal a standard current rating of
an overcurrent protective device, then the marked maxi-
mum rating is to be the next lower standard rating. How-
ever, if the device selected for MOP is less than the
MCA, then select the lowest standard maximum fuse
size greater than or equal to the MCA.

TABLE 24 – COMPRESSOR DATA

Compressor Nominal Voltage

Model

Quantity

Model

400/3/50

per Unit

RLA

LRA

50

4

SZ160

24.2

135

55

4

SZ160

24.2

135

60

4

SZ185

27.9

175

65

4

SZ185

27.9

175

70

4

SZ125

17.9

120

2

SZ160

24.2

135

75

4

SZ125

17.9

120

2

SZ160

24.2

135

80

6

SZ160

24.2

135

85

6

SZ160

24.2

135

90

2

SZ160

24.2

135

4

SZ185

27.9

175

95

2

SZ160

24.2

135

4

SZ185

27.9

175