beautypg.com

Exhaust fan data – York ECO R-22 User Manual

Page 48

background image

YORK INTERNATIONAL

48

TOTAL STATIC PRESSURE (Pascals of water column)

m3/hr

311

373

435

478

STD. AIR

kW

RPM

kW

RPM

kW

RPM

kW

RPM

13592

2.6

810

3.0

873

3.4

933

3.9

992

20388

5.6

924

6.1

976

6.6

1025

7.2

1072

27184

1.4

1055

11.2

1104

12.0

1150

12.7

1196

33980

TOTAL STATIC PRESSURE (Pascals of water column)

m3/hr

62

124

187

249

STD. AIR

kW

RPM

kW

RPM

kW

RPM

kW

RPM

13592

1.2

498

1.6

598

1.9

675

2.3

744

20388

3.7

694

3.9

732

4.5

804

5.9

867

27184

8.4

906

8.8

930

9.2

957

9.6

996

33980

16.6

1141

17.7

1161

Exhaust Fan Data

TABLE 20 – 50 THROUGH 65 TON EXHAUST FAN DATA (CONT’D)

NOTE: * Grey areas indicate operation in motor service factor.

TABLE 20 – 50 THROUGH 65 TON EXHAUST FAN DATA

EXHAUST FAN MOTOR SIZING INSTRUCTIONS

In order to determine the proper exhaust fan motor size,
add the return duct static pressure to the appropriate
damper pressure drop value in Table 23 to get the total
static pressure applied to the exhaust fan. Based on
the exhaust fan air flow and total static pressure, deter-
mine the brake horsepower and RPM of the exhaust
fan.