5°c air on condenser coil, 1°c air on condenser coil – York ECO R-22 User Manual
Page 25

FORM 100.50-EG3 (802)
25
YORK INTERNATIONAL
TABLE 6 – COOLING PERFORMANCE DATA* – 70 TON MODEL (CONT’D)
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
221
185
220
159
218
139
218
119
216
100
–
–
27184
19
216
215
205
196
204
174
204
153
202
134
201
114
17
219
219
205
204
201
199
191
186
187
169
187
149
22
231
203
229
173
227
150
227
129
225
108
–
–
33980
19
232
242
218
216
213
191
212
167
211
145
209
123
17
236
235
224
226
216
222
204
204
196
184
195
161
22
234
215
232
182
230
157
230
133
228
111
–
–
37378
19
237
247
225
231
217
201
215
175
214
151
212
127
17
241
241
230
233
221
227
211
216
200
194
198
169
22
235
217
232
183
230
158
230
134
228
111
–
–
38228
19
238
248
226
233
217
203
216
176
214
152
213
128
17
242
242
232
234
221
228
212
218
201
195
199
170
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
215
184
213
157
212
138
211
118
209
99
–
–
27184
19
213
211
202
194
198
172
197
152
196
133
195
113
17
215
215
202
201
197
195
188
184
183
168
181
148
22
222
200
220
169
219
147
217
125
216
104
–
–
33980
19
224
234
209
212
205
187
204
163
202
141
201
119
17
228
228
215
217
209
215
196
200
189
181
187
158
22
225
211
223
178
221
153
220
129
218
107
–
–
37378
19
229
239
216
226
208
197
206
171
205
147
203
123
17
233
233
221
224
213
219
202
211
192
190
190
165
22
226
213
223
179
222
154
221
130
219
107
–
–
38228
19
230
240
217
228
209
199
207
172
205
148
204
124
17
234
234
222
225
214
220
204
213
193
192
191
167