beautypg.com

Application data, Continued) – York ECO R-22 User Manual

Page 10

background image

YORK INTERNATIONAL

10

The curb should be located according to the location
recommendations above, and properly sealed to pre-
vent moisture and air leakage into and out of the duct
system. Flexible collars should be used when connect-
ing the duct work to prevent unit noise transmission
and vibration into the building.

Duct work should be supported independently of the
unit.

ACOUSTICAL CONSIDERATIONS

The eco

2

unit is designed for lower sound levels than

competitive units by using flexible fan connections, fan
spring isolators, double-wall construction, and lower
speed and horsepower fans. For VAV applications,
VFDs are used instead of inlet guide vanes. Additional
sound attenuation can be obtained using compressor
sound blankets and field-supplied sound attenuators
when necessary.

Even with these equipment design features, the acous-
tical characteristics of the entire installation must never
be overlooked. Additional steps for the acoustical char-
acteristics of a rooftop installation should be addressed
during the design phase of a project to avoid costly al-
terations after the installation of the equipment. During
the design phase of a project, the designing engineer
should consider, at a minimum, the impact of the equip-
ment location, rooftop installation, building structure, and
duct work.

SELECTION PROCEDURE

Given:

Total Cooling Load

920 mbh

Sensible Heat

610 mbh

Required Heating Capacity

875 mbh

Design Cooling Ambient Temp.

95°F

Indoor Air Temperature

80°F db/67°F wb

Supply Air Flow

24,000 cfm

External Static Pressure

2.25 in. w.c.

Electrical Service

460V/3ph/60 Hz

Unit Configuration/Options: 0-100% modulating econo-
mizer, barometric relief, premium efficiency supply fan
motor and VFD, and two-inch pleated filters, bottom
supply, bottom return.

Select Unit:

1. Determine the internal static pressure drop of the

cabinet by referencing Table 17.

Wet evaporator coil

0.58

Bottom return opening

0.15

Two-inch pleated filters

0.12

Mod. econ. dampers

0.56

Total

1.41 IWG

2. Determine the total static pressure by adding the

internal to the external static pressure.

TSP = 1.41 IWG + 2.25 IWG = 3.66 IWG total static pressure

3. Determine the BHP of the supply fan from Table 15

using the supply air flow and total static pressure.
From the table, we interpolate to get 26.3 BHP at
724 rpm.

4. Determine the motor heat gain of supply air flow by

first calculating the motor energy and converting it
into Btuh.

Motor Energy

Motor kW = BHP x .746/efficiency

Motor kW = 26.3 x 0.746/0.94

Motor kW = 20.9 kW

Motor Heat Rejection (MHR)

MHR = 2545 x BHP/efficiency

MHR = 2545 x 26.3/0.94

MHR = 71.2 mbh

5. Calculate actual required total cooling capacity by

adding specified cooling capacity to motor heat
rejection.

Required Total Cooling Capacity

920 mbh + 71.3 mbh = 991 mbh

Required Sensible Cooling Capacity

610 mbh + 71.3 mbh = 681 mbh

Application Data

(continued)