TABLE 2 – COOLING PERFORMANCE DATA* – 50 TON MODEL (CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
175
136
175
119
174
105
173
93
173
80
–
–
22653
19
164
154
162
142
160
128
160
114
160
102
159
90
17
168
168
161
163
150
147
150
135
148
126
147
111
22
176
138
176
120
174
106
174
94
173
81
–
–
25485
19
165
156
163
144
161
130
161
115
161
103
160
90
17
169
169
162
164
152
149
151
137
149
127
148
113
22
177
140
176
122
175
108
175
95
174
81
–
–
29733
19
167
160
164
146
162
132
162
117
162
104
161
91
17
171
171
164
166
154
152
152
140
150
129
149
114
22
181
149
180
129
179
113
178
98
177
83
–
–
31148
19
175
177
169
157
167
141
166
125
165
109
164
94
17
179
179
171
173
163
164
155
151
153
137
152
120
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32
30
28
27
25
23
m3/hr
WB (°C)
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
CAP
SHC
22
168
133
167
115
165
101
164
90
163
78
22653
19
159
153
155
138
154
126
152
112
151
99
151
87
17
161
161
154
156
145
147
142
132
140
123
139
109
22
169
135
168
116
166
102
165
90
164
78
–
–
25485
19
160
156
156
140
154
127
153
113
152
100
151
87
17
163
163
155
157
147
149
143
135
140
124
139
110
22
170
137
169
118
167
104
166
91
165
79
–
–
29733
19
162
158
157
142
155
129
154
114
153
101
152
88
17
165
165
157
158
149
151
144
138
142
126
140
111
22
174
147
172
125
171
109
170
95
169
80
–
–
31148
19
169
172
160
151
160
137
159
121
158
106
156
91
17
172
172
163
165
157
160
150
150
146
134
145
118