beautypg.com

11 feedback control parameters – Toshiba XLTR-200 User Manual

Page 85

background image

84

13.7.11 Feedback Control Parameters

Parameter

Function / Title Bank

Mask

Adjustment Range

Multiplier

0190

FEEDBACK CONTROL

SELECTION

0 / 1

0060

0020: No feedback

(0)

0040: PID control

(1)

0060: Speed feedback

(2)

0191

FEEDBACK INPUT

SIGNAL

SELECTION

0 / 1

001C

0004: RR input

(1)

0008: IV

input

(2)

000C: RX input

(3)

0010: PG

feedback

(4)

0014: RS232C

input

(5)

0018: Communication/12-bit

binary

interface board

(6)

001C: BIN input

(7)

0192

PROPORTIONAL

GAIN

0 / 1

00FF

0001

∼ 00FF (0.01 ∼ 2.55)

0.01

0193

INTEGRAL GAIN

0 / 1

FFFF

0001

∼ 8CA0 (0.01 ∼ 360.00)

0.01

0194

ANTI-HUNTING

GAIN

0 / 1

00FF

0000

∼ 00FF (0.0 ∼ 25.5)

0.1

0195

LAG TIME

CONSTANT

0 / 1

00FF

0000

∼ 00FF (0 ∼ 255)

1

0196

1,

2

PID LOWER LIMIT

FREQUENCY

0 / 1

FFFF

0

∼ Fmax

0.01

0197

PID DEVIATION LIMIT

SELECTION

0 / 1

0080

0000: No PID deviation limit

(0)

0080: PID deviation limited

(1)

0198

PID DEVIATION

UPPER LIMIT

0 / 1

00FF

0000

∼ 0032 (0 ∼ 50)

1

0199

1

PID DEVIATION

LOWER LIMIT

0 / 1

00FF

0000

∼ 0032 (0 ∼ 50)

1

019A

PG INPUT: NUMBER OF

PULSES

0 / 1

FFFF

0001

∼ 270F (1 ∼ 9999)

1

019B

PG INPUT: NUMBER OF

PHASES

0 / 1

0001

0000: Single-phase input

(1)

0001: Two-phase input

(2)

019C

DROOPING CONTROL

ENABLE

0 / 1

0002

0000: OFF

(0)

0002: ON

(1)

019D

1

DROOPING

CONTROL AMOUNT

0 / 1

00FF

0000

∼ 0064 (0 ∼ 10.0)

0.1

019E

OVERRIDE CONTROL

SELECTION

0 / 1

0007

0000: OFF

(0)

0001: FCRR

(1)

0002: FCIV

(2)

0003: FCRX

(3)

0004: FCPG

(4)

0005: FCPNL

(5)

0006: FCOPT

(6)

0007: FCMLT

(7)

019F

OVERRIDE

MULTIPLIER

INPUT SELECTION

0 / 1

0038

0000: Reference

(0)

0008: KRR

(1)

0010: KIV

(2)

0018: KRX

(3)

0020: KBIN

(4)

01A0

7

OVERRIDE CHANGE

MULTIPLIER

0 / 1

FFFF

FC18

∼ 03E8 (-100.0 ∼ 100.0)

0.1

01A1

0203

Reserved