13.7.1 Command Parameters
Parameter
Bit Function Bank
Mask
Adjustment Range
Multiplier
0001 word
Frequency
command 0 FFFF
0.00
∼ 400.00Hz
Actual frequency will be limited by
LL, UL and Fmax.
0.01
0002 0
RUN
command
0
0: Stop
1: Run
1
Reserved
2
Forward
• reverse run
selection
0:
reverse
1: forward
3
Acc/dec #1 / #2
selection
0: Acc / dec #1
1: Acc / dec #2
4
Reserved
5
Reserved
6
Reserved
7
Jog mode selection
0: Normal (acc/dec mode)
1: Jog mode
8
Feedback control
0: Feedback valid
1: Feedback invalid
9
Compulsory
DC
injection braking mode
0: No compulsory DC injection
braking
1: Compulsory DC injection
below DC INJECTION
START FREQUENCY
A
Fundamental
parameter switching
0: V/F #1
1: V/F #2
B
Gate block command
(coast stop command)
0:
Normal
1: Gate block
C
Emergency
off
command
0: Does nothing
1: Emergency off
D
Reset
command
(trip clear)
0: Does nothing
1: Reset
E
Reserved
F
Reserved
0003
word
RS232 command /
frequency selection
0 0003
0000:
FREQUENCY MODE
SELECTION, COMMAND
MODE SELECTION
settings
0001: RS232C commands valid
0002: RS232C frequency valid
0003: RS232C commands and
frequency valid
0004
word
Preset speed run
command
0 000F
0000:
Output
frequency
selected by FREQUENCY
MODE SELECTION
0001
∼ 000F: speeds 1 ∼ 15