Toshiba XLTR-200 User Manual
Page 68
67
Table 5: Input Terminal Status Monitor (parameter 000D)
Bit Input
Terminal
0
1
Single-Bit
Read Mask
bit 0
F
terminal - CC open
terminal - CC shorted
0001
bit 1
R
terminal - CC open
terminal - CC shorted
0002
bit 2
S1
terminal - CC open
terminal - CC shorted
0004
bit 3
S2
terminal - CC open
terminal - CC shorted
0008
bit 4
S3
terminal - CC open
terminal - CC shorted
0010
bit 5
S4
terminal - CC open
terminal - CC shorted
0020
bit 6
S5 (option)
terminal - CC open
terminal - CC shorted
0040
Lower
Byte
bit 7
S6 (option)
terminal - CC open
terminal - CC shorted
0080
Bit Input
Terminal
0
1
Single-Bit
Read Mask
bit 0
unused (always 0)
bit 1
unused (always 0)
bit 2
unused (always 0)
bit 3
unused (always 0)
bit 4
unused (always 0)
bit 5
S7 (option)
terminal - CC open
terminal - CC shorted
0020
bit 6
RES
terminal - CC open
terminal - CC shorted
0040
Upper
Byte
bit 7
ST
terminal - CC open
terminal - CC shorted
0080
Table 6: Output Terminal Status Monitor / Inverter Status 2 (parameter 000E)
Bit Output
Terminal
0
1
Single-Bit
Read Mask
bit 0
unused (always 0)
bit 1
unused (always 0)
bit 2
FAN
OFF
ON
0004
bit 3
FL
FLB-FLC shorted FLA-FLC
shorted 0008
bit 4
MS relay
OFF
ON
0010
bit 5
OUT (option)
OUTB-OUTC shorted
OUTA-OUTC shorted
0020
bit 6
RCH
RCHA-RCHC open
RCHA-RCHC shorted
0040
Lower
Byte
bit 7
LOW
LOWA-LOWC open
LOWA-LOWC shorted
0080
Bit Inverter
Status
0
1
Single-Bit
Read Mask
bit 0
accelerating
not accelerating
accelerating
0001
bit 1
decelerating
not decelerating
decelerating
0002
bit 2
for inverter use
bit 3
retry
not retrying
retrying
0008
bit 4
running (including DC
injection braking)
stopped running
0010
bit 5
for inverter use
bit 6
for inverter use
Upper
Byte
bit 7
tripped
not tripped
tripped
0080