Parameter
Function / Title Bank
Mask
Adjustment Range
Multiplier
0133
STALL PROTECTION
ENABLE
0 / 1
0040
0000: ON
(0)
0040: OFF
(1)
0134
0
STALL
PROTECTION
CURRENT LEVEL
0 / 1
00FF
000A
∼ 00D7 (10 ∼ 215)
1
0135
UNDERVOLTAGE TRIP
SELECTION
0 / 1
0080
0000: Trip disabled
(0)
0080: Trip (during run)
(1)
0136
UNDERVOLTAGE DETECT
TIME
0 / 1
FFFF
0000
∼ 03E8 (0.00 ∼ 10.00)
0.01
0137
LOW CURRENT DETECT
SELECTION
0 / 1
0008
0000: Trip disabled
(0)
0008: Trip on detection
(1)
0138
LOW CURRENT DETECT
LEVEL
0 / 1
00FF
0000
∼ 0064 (0 ∼ 100)
1
0139
LOW CURRENT
DETECTION TIME
0 / 1
00FF
0000
∼ 00FF (0 ∼ 255)
1
0140
OUTPUT SHORT-
CIRCUIT DETECTION
SELECT
0 / 1
0003
0000: Standard motor
(0)
0001: High-speed
motor
(1)
0002: Positioning use (standard
motor) (2)
0003: Positioning use (high-speed
motor) (3)
0141
OVERTORQUE TRIP
SELECTION
0 / 1
0040
0000: Trip disabled
(0)
0040: Trip enabled
(1)
0142
OVERTORQUE TRIP
LEVEL
0 / 1
00FF
0000
∼ 00C8 (0 ∼ 200)
1
0143
FAULT TRIP EEPROM
SAVE ENABLE
0 / 1
0002
0000: Data cleared when powered
OFF (0)
0002: Data retained when powered
OFF (1)
0144
COOLING FAN CONTROL
SELECTION
0 / 1
0004
0000: Automatic (temperature
detection) (0)
0004: Always
ON
(1)
0145
CUMULATIVE RUN
TIMER ALARM SETTING
0 / 1
FFFF
0000
∼ C34B (0.00 ∼ 999.90)
0.02