13.6.2 Supported Subpoints
This application contains a predefined set of FLN subpoints (refer to Table 4).
These points are static for this application, and cannot be edited.
Table 4: Supported Subpoints
Point #
Point
Type
Subpoint
Name
Factory
Default
Units
Slope Intercept
On
Text
Off
Text
01 LAO
ADDRESS
99
–
1
0
–
–
02 LAO APPLICATION 2750 –
1
0
–
–
03 LAI FREQ
OUTPUT
0
HZ 0.01
0
–
–
04 LAI OUTPUT
CUR
0
A 0.01
0
–
–
05 LAI OUTPUT
VOLT
0
V 0.1
0
–
–
06 LAI SPECIAL
MON
0
-
1
0
–
–
07 LAO MON
SELECT
0
-
1
0
–
–
08 LAO ACCEL
TIME
50 SEC 0.1
0
–
–
09 LAO DECEL
TIME
100 SEC 0.1
0
–
–
10
LDO
CMD
FWD.STOP
STOP
– 1 0 FWD
STOP
11
LDO
CMD
REV.STOP
STOP
– 1 0 REV
STOP
12 LAO FREQ
CMD
0
HZ 0.01
0
–
–
13 LAO MIN
FREQ
0
HZ 0.01
0
-
-
14
LAO
FREQ JUMP A
32767
HZ
0.01
0
-
-
15
LAO
FREQ JUMP B
32767
HZ
0.01
0
-
-
16 LDI ALARM
OUTPUT
0
–
1
0 ALARM -
17
LDI RUNNING STOP
– 1 0 RUN
STOP
18
LAO
PID SET PNT
0
PCT
0.01
0
-
-
19 LDO RESET
CMD
0
–
1
0 RESET -
20 LAO OVRD
TIME
1 HRS 1
0
–
–
21
LDI ASD
COMM NO - 1 0 YES
NO
22 LAO OPER
MODE
0
-
1
0
-
-
29 LDO DAY.NIGHT
DAY –
1
0 NIGHT DAY
99 LAO ERROR
STATUS
0
–
1
0
–
–
Notes:
•
Points not listed are not used in this application.
•
All points have the same value for English units and SI units.