61
11. CMD REV.STOP
Commands the drive to run reverse or stop. Note that commanding this point is
effective only when the drive is configured for network start/stop control.
Corresponds to drive command parameter 1014, bit #2.
12. FREQ CMD
The frequency command of the drive in Hertz. Note that commanding this point
is effective only when the drive is configured for network frequency control.
Corresponds to drive parameter 1001.
13. MIN FREQ
The drive’s minimum allowable frequency in Hertz. Corresponds to drive
parameter 2.
14. FREQ JUMP A
Sets the lower limit of the jump frequency for area #1. An FLN object value of
32767 for this point corresponds to an internal drive value of 9999 (disabled).
Corresponds to drive parameter 31.
15. FREQ JUMP B
Sets the upper limit of the jump frequency for area #1. An FLN object value of
32767 for this point corresponds to an internal drive value of 9999 (disabled).
Corresponds to drive parameter 32.
16. ALARM OUTPUT
Indicates whether or not the drive is in an alarm condition. Corresponds to
drive status parameter 1014, bit #7.
17. RUNNING
Indicates whether or not the drive is running. Corresponds to drive status
parameter 1014, bit #0.
18. PID SET PNT
PID set point. Note that commanding this point is effective only when the drive
is in the PU operation or PU/external combined mode. Corresponds to drive
parameter 133.
19. RESET CMD
Drive fault reset command. Corresponds to drive parameter 1017.
20. OVRD TIME
This is a mandatory FLN point required for compatibility with Siemens control
systems. It has no effect in this application.
21. ASD COMM
Drive network communications health indicator. This point has a value of
“YES” if the gateway is successfully communicating with the attached drive.
Status points read from the gateway should be disregarded whenever this