13.7.3 Fundamental Parameters #1
Parameter
Function / Title Bank
Mask Adjustment Range
Multiplier
0026
MAXIMUM OUTPUT
FREQUENCY (*)
0 / 1
FFFF
0BB8
∼ 9C40 (30.00∼400.00)
0.01
0027
BASE FREQUENCY #1
0 / 1
FFFF
09C4
∼ 9C40 (25.00∼400.00)
0.01
0028
BASE FREQUENCY
VOLTAGE SELECT (*)
0 / 1
0030
0000: Input voltage level
(0)
0020: Automatic setting
(1)
0030: Stationary setting
(2)
0029
MAXIMUM OUTPUT
VOLTAGE #1
0 / 1
FFFF
0000
∼ 0258 (0 ∼ 600)
1
002A
REVERSE OPERATION
DISABLE SELECT
0 / 1
0020
0000: Reverse allowed
(0)
0020: Reverse not allowed
(1)
002B
UPPER LIMIT FREQUENCY
0 / 1
FFFF
0000 ~ Fmax
0.01
002C
LOWER LIMIT FREQUENCY
0 / 1
FFFF
0000
∼ UL, Fmax
0.01
002D
VOLTS PER HERTZ
PATTERN (*)
0 / 1
000F
0000: Constant torque
(1)
0001: Variable torque
(2)
0002: Auto. torque boost
(3)
0006: #3 w/ auto. energy savings (4)
000A: Vector control
(5)
000E: #5 w/ auto. energy savings (6)
002E
1, 2
VOLTAGE BOOST
#1
0 / 1
FFFF
0000
∼ 012C (0.0 ∼ 30.0)
0.1
002F
ACCELERATION TIME #1
0 / 1
FFFF
0001
∼ EA60 (0.01~ 600.00)
0001
∼ EA60 (0.1~ 6000.0)
0.01
0.1
0030
DECELERATION TIME #1
0 / 1
FFFF
0001
∼ EA60 (0.01~ 600.00)
0001
∼ EA60 (0.1~ 6000.0)
0.01
0.1
0031
ACC/DEC PATTERN #1
SELECTION
0 / 1
0030
0000: Linear
(0)
0010: Self-adjusting
(1)
0020: S-Pattern #1
(2)
0030: S-Pattern #2
(3)
0032
ACCEL/DECEL PATTERN
ADJUST LOW
0 / 1
00FF
0003 ~ 00FD (0
∼ 50) (Note 1)
1
0033
ACCEL/DECEL PATTERN
ADJUST HIGH
0 / 1
00FF
0003 ~ 00FD (0
∼ 50) (Note 1)
1
Note 1:
Parameter data = (desired setting x 5 + 3), converted to hexadecimal