2 monitor parameters – Toshiba XLTR-200 User Manual
Page 66
65
13.7.2 Monitor Parameters
Parameter
Bit Function
Bank
Mask
Adjustment Range
Multiplier
0005
word
Output frequency monitor
0
FFFF
0.00 ~ 400.00Hz
0.01
0006 0
Run
• stop status
0
0: Stopped
1: Running
1
Reserved
2
Forward
• reverse status
0:
Reverse
1: Forward
3
Accel / decel #1 / #2 selection
status
0: Accel / decel #1
1: Accel / decel #2
4
Reserved
5
Reserved
6
Reserved
7
Jog mode status
0: Normal (accel /
decel mode)
1: Jog mode
8
Feedback enable status
0: Feedback invalid
1: Feedback valid
9
Compulsory DC injection
braking mode
0: DC injection braking
inactive
1: DC injection braking
active
A
Fundamental
parameter
switching
0: V/F #1
1: V/F #2
B
Coast stop command status
0: Normal
1: Coast to stop
C
Emergency off command
0: Normal
1: Emergency off
D
Reserved
E
Reserved
F
Reserved
0007
word
Output current monitor
0
00FF
0 ~ 255%
1
0008
word
Output voltage monitor (Note
1)
0
FFFF
0 ~ 232%
0.1
0009
word
IV terminal analog input value
0
FFFF
0000 ~ FFFF (0% ~
100%)
1
000A
word
RX terminal analog input
value
0 FFFF
0000 ~ 7FFF (-100% ~
0%), 7FFF ~ FFFF
(0% ~ 100%)
1
000B
word
Frequency command monitor
0
FFFF
0000
∼ 9C40
(0.00
∼ 400.00 Hz)
0.01
000C
word
Input voltage monitor (Note 1)
0
FFFF
0 ~ 255%
0.1
000D
word
Input terminal status monitor
0
FFFF
Refer to Table 5 (page
67)
000E low
byte
Output terminal status
monitor
0
00FF
Refer to Table 6 (page
67)
high
byte
Inverter Status 2
FF00
000F
word
Inverter Status 1
0
FFFF
Refer to Table 7 (page
68)
0010 word
Present
trip
0
00FF
0011 high
byte
4th Past trip (most recent)
0
7F00
low
byte
3rd past trip
007F
Refer to section
13.7.16 for fault codes