Toshiba XLTR-200 User Manual
Page 37

36
Modbus Master Point Attributes
Figure 16: Edit Modbus Master Attributes
•
Edit Address: Menu selection 1 allows you to edit the network 
address of the Modbus slave that this point refers to. 
•
Edit Register: Menu selection 2 allows you to edit the Modbus 
holding register or input register that this point will access. The type of 
register accessed (holding or input) will be determined on the basis of 
the “Read FC” setting (see below). Figure 16 shows an example of 
how to change the current setting of holding register 1 to holding 
register 50. 
•
Read FC: Menu selection 3 allows you to choose the Modbus “read” 
function code that will be used to read from the designated register. 
The default setting of function code 03 (read holding registers) will 
access a holding register on the remote device. By selecting function 
code 04 (read input registers), a Modbus input register will be 
accessed instead. 
•
Write FC: Menu selection 4 allows you to choose the Modbus “write” 
function code that will be used to write to the designated holding 
register (this setting does not apply to input registers, as they are 
read-only). The default setting is function code 16 (preset multiple 
registers). Alternatively, this setting can be changed to function code 
06 (preset single register) in order to connect to those Modbus slave 
devices that do not support function code 16. 
