beautypg.com

Toshiba XLTR-200 User Manual

Page 67

background image

66

Parameter

Bit Function

Bank

Mask

Adjustment Range

Multiplier

0012 high

byte

2nd past trip

0

7F00

low

byte

1st past trip (oldest)

007F

0013 word

Pre-compensation

output

frequency

0 FFFF

0000

∼ 9C40

(0.00

∼ 400.00 Hz)

0.01

0014 word

Post-compensation

output

frequency

0 FFFF

0000

∼ 9C40

(0.00

∼ 400.00 Hz)

0.01

0015

word

Torque current monitor

0

FFFF

(Note 2)

0.01

0016 low

byte

Excitation current monitor

0

00FF

00

∼ FF (0 ~ 255%)

1

high

byte

Reserved

0017

word

PID feedback value

0

FFFF

(Note 2)

0.02

0018

word

Motor overload ratio

0

FFFF

0 ~ 65535

100/65535

0019

word

Inverter overload ratio

0

FFFF

0 ~ 65535

100/65535

001A

word

DBR overload ratio

0

FFFF

0 ~ 65535

100/65535

001B

word

Input power (%)

0

FFFF

0 ~ 6553.5

0.1

001C

word

Input power (kW)

0

FFFF

(Note 3)

001D

word

Output power (%)

0

FFFF

(Note 2)

0.1

001E

word

Output power (kW)

0

FFFF

(Note 2, Note 3)

001F

word

RR input

0

FFFF

0 ~ 65535

100/65535

0020

Reserved

0021

Reserved

0022

Reserved

0023 low

byte

Inverter typeform monitor

0

00FF

Refer to Table 8 (page
68)

8

Input / output power units

0

0100

0: 0.01kW
1: 0.1kW

9,A

Command mode status

0

0600

00: terminal
01: panel
10: option
11: RS232C

B,C

Frequency mode selection
status

0 1800

00:

terminal

01: panel
10: option
11: RS232C

D,E,F

Reserved

0024

Reserved

0025

word

Output current (amps)

FFFF

0.0 ~ 6553.5 A

0.1

(Note 1) .... These monitor voltage units are not affected by the setting of VOLTAGE UNITS SELECTION in

GROUP:UTILITY PARAMETERS; they are always in units of %.

(Note 2) .... These parameters use signed data (data values larger than 7FFF

H

are negative). If the parameter data is

8000

H

or larger, the actual value can be obtained by: actual value = - [FFFF

H

- (parameter data) + 1].

(Note 3) .... If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is 0.01.

If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier is 0.1.
These values are automatically set according to the inverter’s capacity.