beautypg.com

Toshiba Tosvert EtherNet/IP - Modbus TCP option IPE002Z User Manual

Page 79

background image

E6581741

- 78 -

<

Example of setting>

The example below shows how to configure the local/remote operation.

F terminal ............... Operating command

R terminal ............... EtherNet/IP-

Modbus TCP

local/remote

(Terminal in this example) switching

VIA terminal ........... Operation frequency command

VF-MB1

F

R

CC

PP

VIA

Variable resistor for adjustment

10k ohm

EtherNet/IP-Modbus TCP

/local Switch

Operation command

SINK

SW1*

SOURCE

CC

PLC

cmod

(Command mode selection) = 0 (Terminal board)

fmod

(Frequency setting mode selection 1) = 1 (VIA)

f112

(Input terminal selection 2 (R)) = 48 (Remote/Local control)

R-CC terminal open: VF-MB1 is controlled as a slave device of the EtherNet/IP™ -

Modbus

®

TCP.

R-CC terminal closed:

F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the VIA signal input.

(Note)

When the local(HAND) / remote key (f750=2) is chosen as EASY key selection and

the EASY key lamp of an inverter front panel is on, priority is most given to operation by

a panel. (Refer to the inverter instruction manual for details).