■Examples of Instance 101/151
Access the inverter parameter is enabled using byte 4 to 6 of this Instance.
Set the communication number of the parameter to byte 4, 5 (Index), and the value to byte 6, 7 (Data).
c Read the parameter cmod (Command mode selection, communication number is 0003).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
5, 4
0
0
0
0
0
0 0 0 0
0
0
0
0
0
1 1
0x0003
Output Instance 101
7, 6
-
-
-
-
-
-
- -
-
-
-
-
-
-
-
-
-
Input Instance 151
5, 4
0 0 0
0
0
0 0 0 0
0
0
0
0
0
1 1
0x0003
(cmod is 0.)
7, 6
0
0
0
0
0
0 0 0 0
0
0
0
0
0
0
0
0x0000
d Read the parameter f268 (Initial value of UP/DOWN frequency).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
5, 4
0
0
0
0
0
0 1 0 0 1
1
0
1
0 0 0 0x0268
Output Instance 101
7, 6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Input Instance 151
5, 4
0 0 0
0
0
0 1 0 0 1
1
0
1
0 0 0 0x0268
(f268 is 60.0Hz.)
7, 6
0 0 0
1
0
1
1
1
0 1
1
1
0 0 0 0 0x1770
3 Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
5, 4
1
0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x8018
Output Instance 101
7,
6 0 0 0
1
0
1
1
1
0 1
1
1
0 0 0 0 0x1770
5, 4
1
0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x8018
Input Instance 151 (OK)
7,
6 0 0 0
1
0
1
1
1
0 1
1
1
0 0 0 0 0x1770
Input Instance 151 (NG)
5, 4
1 1
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0xC018
(Error code *)
7, 6
0 0 0
1
0
0 0 1 0 0
0
0
0 0 0 0 0x1100
*Data of "Error code"
0x1100: Data out of range
0x1101: Bad address