3.2.2.

Assigning IP addresses (c504, c505-c516)

The drive needs 3 (4-Modbus TCP) IP addresses.

*The drive IP address.
*The subnet mask.
*The gateway IP address.
(*The IP Master address.- Modbus TCP protocol only)


These parameters are effective settings at c504 = 0 (IP mode: Manual).
If the address has been given by a BOOTP or a DHCP server, these parameters are
invalidity.
• After dynamic addressing by a BOOTP or DHCP server, the new address value is

displayed in the parameters. (c524-c535)


They can be provided by:

*BOOTP server (correspondence between the MAC address and the IP addresses).
*DHCP server (correspondence between Device Name and the IP addresses).


The address is assigned according to the IP mode parameter.

c504: IP mode

Comments

0

The option uses the address defined in c505-c516.

1

The option receives its address from a BOOTP server.

2

The option receives its address from a DHCP server.
*Device name contains (c081-c096) a valid name.

Note: The IP mode parameter may be modified according to the configuration control

attribute of the TCP/IP interface object (CIP standard).