Parameter objects (0x65) – Toshiba Tosvert EtherNet/IP - Modbus TCP option IPE002Z User Manual
Page 36
E6581741
- 35 -
4.9. Parameter Objects (0x65)
Class code 0x65. This object provides VF-MB1/S15’s Parameter access.
Range Address accessed:
Input Instance
Real Logical address in Drive accessed
0x0001-0xFFFF 0x0001-0xFFFF
* Refer to "Class Attributes" when the instance is 0.
* If you want to access the au1, please use the "Application Objects (64 hex)."
Class Attributes
Instance Attribute ID Access
Name
Data type
Details
Value
1
Get
Revision
UINT
Revision of this object
1
2 Get Max
Instances
UINT Maximum instance number of an
object currently created in this class
level of the device.
65535
3
Get
Number of Instances
UINT
Number of object instances currently
created at this class level of the
device.
65535
6
Get
Max ID of class
attributes
UINT
The attribute ID number of the last
class attribute of the class definition
implemented in the device.
7
0
7
Get
Max ID of instance
attribute
UINT
The attribute ID number of the last
instance attribute of the class
definition implemented in the device.
3
Class Services
Service Code
Service Name
Description of Service
0x0E Get_Attribute_Single Read one attribute
Instance 1 Attribute
Instance Attribute ID Access
Name
Data type
Details
See
below
3 Get/Set
parameter
UINT
Parameter corresponding to the Instance
address
Instance Services
Service Code
Service Name
Description of Service
0x0E Get_Attribute_Single Read one attribute
0x10 Set_Attribute_Single Write one attribute
Attribute ID of all parameters are 3. Moreover, about the instance ID of each parameter, it
becomes "parameter communication number".
About the details of the contents of a parameter please refer to VF-MB1 instruction
manual or VF-S15 instruction manual.
Example 1:
When "ACC. time" is set to 5 s, since the minimum unit is 0.1s,
5 / 0.1 = 50 = 32H
Since the communication umber of "Acc. time" is "0009", it writes "32H" is instance ID "0009."