Toshiba Tosvert EtherNet/IP - Modbus TCP option IPE002Z User Manual
Page 54
E6581741
- 53 -
■Examples of Instance 105/155
Access the inverter parameter is enabled using byte 1 to 5 of this Instance.
Set the communication number of the parameter to byte 2, 3 (Index), and the value to byte 4, 5 (Data).
c Read the parameter cmod (Command mode selection, communication number is 0003).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
1, 0
0
0
0
0
0
0 0 0 0
0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 0 0 0
0
0
0
0
0
1 1
0x0003
Output Instance 105
5, 4
-
-
-
-
-
-
- -
-
-
-
-
-
-
-
-
-
1, 0
0
0
0
0
0
0 0 0 0
0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 0 0 0
0
0
0
0
0
1 1
0x0003
Input Instance 155
(cmod is 0.)
5, 4
0
0
0
0
0
0 0 0 0
0
0
0
0
0
0
0
0x0000
d Read the parameter f268 (Initial value of UP/DOWN frequency).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
1, 0
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 1 0 0 1
1
0
1
0 0 0 0x0268
Output Instance 105
5, 4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1, 0
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 1 0 0 1
1
0
1
0 0 0 0x0268
Input Instance 155
(f268 is 60.0Hz.)
5,
4 0 0 0
1
0
1
1
1
0 1
1
1
0 0 0 0 0x1770
3 Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018).
Instance
Byte 15 14 13 12 11 10 9
8
7
6
5
4
3 2 1 0
Hex.
1, 0
1
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x8000
3, 2
0 0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x0018
Output Instance 105
5,
4 0 0 0
1
0
1
1
1
0 1
1
1
0 0 0 0 0x1770
1, 0
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x0000
3, 2
0
0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x0018
Input Instance 155
(OK)
5,
4 0 0 0
1
0
1
1
1
0 1
1
1
0 0 0 0 0x1770
1, 0
0 1
0
0
0
0 0 0 0 0
0
0
0
0
0
0
0x4000
3, 2
0
0
0
0
0
0 0 0 0 0
0
1
1
0 0 0 0x0018
Input Instance 155
(NG)
(Error code *)
5, 4
0
0
0
0
0
0 0 0 0 0
0
0
0
0
0
1
0x0001
*Data of "Error code"
0x0001: Error