Fc91 (alarm code), Fd06 (input tb status) – Toshiba Tosvert EtherNet/IP - Modbus TCP option IPE002Z User Manual
Page 21
E6581741
- 20 -
3.2.4.13. fc91 (Alarm code)
bit
Function
0
1
Remarks
(Code displayed on
the panel)
0 Over-current
alarm
Normal Alarming c flicking
1
Inverter over load alarm
Normal Alarming l flicking
2
Motor over load alarm
Normal Alarming l flicking
3
Over heat alarm
Normal Alarming h flicking
4
Over voltage alarm
Normal Alarming p flicking
5
Main circuit undervoltage alarm
Normal Alarming
-
6
main device overheat alarm
Normal Alarming l flicking
7
Under current alarm
Normal Alarming
-
8 Over-torque
alarm
Normal Alarming
-
9
Braking resistor overload alarm
Normal Alarming
-
10
Cumulative operation hours alarm
Normal Alarming
-
11
Option communication alarm
Normal Alarming
-
12
Serial communication alarm
Normal Alarming
-
13
MOFFMS (MSrelay off or MOFF)
Normal Alarming
-
14
Stop after instantaneous power off
-
Dec., Under
stop
Refer to f302
value
15
Stop after LL continuance time
-
Dec., Under
stop
Refer to f256
value
3.2.4.14. fd06 (Input TB Status)
bit
TB Name
Function (Parameter)
0
1
0
F
Input terminal function selection 1 (f111)
1
R
Input terminal function selection 2 (f112)
2
RES
Input terminal function selection 3 (f113)
3
S1
Input terminal function selection 4 (f114)
4
S2
Input terminal function selection 5 (f115)
5
S3
Input terminal function selection 6 (f116)
6
VIB*1
Input terminal function selection 7 (f117)
7
VIA*1
Input terminal function selection 8 (f118)
OFF ON
5 to 15
(Reserved) -
Undefined
Note: Don't use the reserved bit for the judgment.
*1: VIA/ VIB are input terminal function when f109 is logic input.
*The input terminal function is selected by each parameter.
Example: Data set for FE06 when the F and RES terminals are ON = 0005H
BIT15 BIT0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
FE06:
0
0
0
5