Fd01 (inverter operating status 1), Fd00 (output frequency) – Toshiba Tosvert EtherNet/IP - Modbus TCP option IPE002Z User Manual

Page 19

background image

E6581741

- 18 -

3.2.4.7. fd01 (Inverter operating status 1)

bit Function

0

1

Note

0

Failure FL

No output

Under in

progress

-

1 Failure

Not

tripped

Tripped

Trip status includes rtry and
the trip retention status are also
regarded as tripped statuses.

2

Alarm

No alarm

Alarm issued

-

3

Under voltage (moff) Normal Under

voltage

-

4

Motor selection (1 or 2)
(THR 2 selection)

Motor 1 (THR1)

Motor 2 (THR2)

THR1: pt = setting value, vl,
vlv

, vb, thr

THR2: pt = 0, f170, f171,
f172

, f173

5

PID control off

PID control

permitted

PID control

prohibits

-

6

Acceleration/deceleratio
n pattern selection (1 or
2)

Acceleration/dec

eleration pattern

1 (AD1)

Acceleration/dec

eleration pattern

2 (AD2)

AD1: acc, dec
AD2: f500, f501

7 DC

braking

OFF

Forced DC

braking

-

8

Jog run

OFF

Jog run

-

9

Forward / reverse run

Forward run

Reverse run

-

10 Run/stop

Stop

Run

-

11

Coast stop (ST = OFF)

ST=ON

ST=OFF

-

12 Emergency

stop

No emergency

stop status

Emergency

stop status

-

13

Standby ST=ON

Start-up process

Standby

Standby: Initialization
completed, not failure stop
status, not alarm stop status
(moff, ll forced stop),
ST=ON, and RUN=ON

14 Standby

Start-up

process

Standby

Standby: Initialization completed,
not failure stop status and not
alarm stop status (moff, ll
forced stop)

15 (Reserved)

Undefined

-

Note: Don’t use the reserved bit for the judgment.

3.2.4.8. fd00 (Output frequency)


The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.

Since the minimum unit is 0.01%,

0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)


Also about the following parameters, these are the same as this.

- fd22 (Feedback value of PID)............................................... Unit: 0.01Hz
- fd16 (Estimated speed) ........................................................ Unit: 0.01Hz
- fd29 (Input power) ................................................................ Unit: 0.01kW
- fd30 (Output power) ............................................................. Unit: 0.01kW