Iii. unit start-up (cont) – Sterling AquaSnap 30RA010-055 User Manual
Page 99

CL-7
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
SLCT (Setpoint and Ramp Load Configuration)
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.
RECORD CONFIGURATION INFORMATION BELOW:
SETPOINT
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
SLCT
SETPOINT AND RAMP LOAD
CLSP
X
COOLING SETPOINT SELECT
RL.S
ENBL/DSBL
RAMP LOAD SELECT
CRMP
X.X
COOLING RAMP LOADING
SCHD
XX
SCHEDULE NUMBER
Z.GN
X.X
DEADBAND MULTIPLIER
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
COOL
COOLING SETPOINTS
CSP.1
XXX.X °F
COOLING SETPOINT 1
CSP.2
XXX.X °F
COOLING SETPOINT 2
CSP.3
XXX.X °F
ICE SETPOINT
HEAD
HEAD PRESSURE SETPOINTS
HD.P.A
XXX.X °F
CALCULATED HP SETPOINT A
HD.P.B
XXX.X °F
CALCULATED HP SETPOINT B
FRZ
BRINE FREEZE SETPOINT
BR.FZ
XXX.X °F
BRINE FREEZE POINT