Table 38 — Motormaster® V Program Parameters for Operating Modes
LEGEND
PARAMETERS
DESCRIPTION
MODE
1
MODE
2
MODE
3
MODE
4
P01
Line Voltage: 01 = low line, 02 = high line
01
02
01
02
P02
Sterlco Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz 01 01 01 01
P03
Startup mode: flying restart
06
06
06
06
P04
Stop mode: coast to stop
01
01
01
01
P05
Standard Speed source: 01= keypad,
04=4-20mA (NO PI), 05= R22, 06=R134a
05
05
05
05
P06
TB-14 output: 01 = none
01
01
01
01
P08
TB-30 output: 01 = none
01
01
01
01
P09
TB-31 Output: 01 = none
01
01
01
01
P10
TB-13A function sel: 01 = none
01
01
01
01
P11
TB-13B function sel: 01 = none
01
01
01
01
P12
TB-13C function sel: 01 = none
01
01
01
01
P13
TB-15 output: 01 = none
01
01
01
01
P14
Control: 01 = Terminal strip
01
01
01
01
P15
Serial link: 02 = enabled 9600,8,N,2 with timer
02
02
02
02
P16
Units editing: 02 = whole units
02
02
02
02
P17
Rotation: 01 = forward only, 03 = reverse only
01
01
01
01
P19
Acceleration time: 10 sec
10
10
10
10
P20
Deceleration time: 10 sec
10
10
10
10
P21
DC brake time: 0
0
0
0
0
P22
DC BRAKE VOLTAGE 0%
0
0
0
0
P23
Min freq = 8 Hz ~ 100 – 160 rpm
8
8
8
8
P24
Max freq
60
60
50
50
P25
Current limit: (%)
125
110
125
110
P26
Motor overload: 100
100
100
100
100
P27
Base freq: 60 or 50 Hz
60
60
50
50
P28
Fixed boost: 0.5% at low frequencies
0.5
0.5
0.5
0.5
P29
Accel boost: 0%
0
0
0
0
P30
Slip compensation: 0%
0
0
0
0
P31
Preset spd #1: speed if loss of control signal
57
57
47
47
P32
Preset spd #2: 0
0
0
0
0
P33
Preset spd #3: 0
0
0
0
0
P34
Preset spd 4 default — R22 set point.
TB12-2 open
18.0
18.0
18.0
18.0
P35
Preset spd 5 default — R134a set point.
TB12-2 closed
12.6
12.6
12.6
12.6
P36
Preset spd 6 default
0
0
0
0
P37
Preset spd 7 default
0
0
0
0
P38
Skip bandwidth
0
0
0
0
P39
Speed scaling
0
0
0
0
P40
Frequency scaling 50 or 60 Hz
60
60
50
50
P41
Load scaling: default (not used so NA)
200
200
200
200
P42
Accel/decel #2: default (not used so NA)
60
60
60
60
P43
Serial address
1
1
1
1
P44
Password:111 111
111
111
111
P45
Speed at min signal: 8 Hz; used when PID
mode is disabled and 4-20mA input is at 4 mA
8
8
8
8
P46
Speed at max feedback: 60 or 50 Hz. Used
when PID disabled and 4-20mA input is at 20 mA
60
60
50
50
P47
Clear history? 01 = maintain. (set to 02 to clear)
01
01
01
01
P48
Program selection: Program 1 – 12
01
02
03
04
P61
PI Mode: 05= reverse, 0-5V, 01 = no PID
05
05
05
05
P62
Min feedback = 0 (0V *10)
0
0
0
0
P63
Max feedback = 50 (5V * 10)
50
50
50
50
P64
Proportional gain = 4%
4
4
4
4
P65
Integral gain = .2
.2
.2
.2
.2
P66
PI acell/decel (set point change filter) = 5
5
5
5
5
P67
Min alarm
0
0
0
0
P68
Max alarm
0
0
0
0
NA
— Not Applicable
PID — Proportional Integral Derivative
TB