Alarms and alerts – Sterling AquaSnap 30RA010-055 User Manual
Page 53

53
Alarms and Alerts —
These are warnings of abnormal
or fault conditions, and may cause either one circuit or the
whole unit to shut down. They are assigned code numbers as
described in Table 29.
Automatic alarms will reset without operator intervention if
the condition corrects itself. The following method must be
used to reset manual alarms:
Before resetting any alarm, first determine the cause of the
alarm and correct it. Enter the Alarms mode indicated by the
LED on the side of the Scrolling Marquee Display. Press
and
until the sub-menu item RCRN “RESET
ALL CURRENT ALARMS” is displayed. Press
.
The control will prompt the user for a password, by displaying
PASS and WORD. Press
to display the default pass-
word, 1111. Press
for each character. If the password
has been changed, use the arrow keys to change each individu-
al character. Toggle the display to “YES” and press
.
The alarms will be reset.
Table 29 — Alarm and Alert Codes
ENTER
ENTER
ENTER
ENTER
ENTER
ALARM/
ALERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM
GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
T051
Alert
Circuit A, Compressor 1
Failure
Compressor feedback signal
does not match relay state
Compressor A1 shut
down.
Manual
High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.
T052
Alert
Circuit A, Compressor 2
Failure
Compressor feedback signal
does not match relay state
Compressor A2 shut
down.
Manual
High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.
T055
Alert
Circuit B, Compressor 1
Failure
Compressor feedback signal
does not match relay state
Compressor B1 shut
down.
Manual
High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.
T056
Alert
Circuit B, Compressor 2
Failure
Compressor feedback signal
does not match relay state
Compressor B2 shut
down.
Manual
High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.
A060
Alarm
Cooler Leaving Fluid
Thermistor Failure (T1)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Chiller shutdown
immediately
Automatic Thermistor failure, damaged
cable/wire or wiring error.
A061
Alarm
Cooler Entering Fluid
Thermistor Failure (T2)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Chiller shutdown
immediately
Automatic Thermistor failure, damaged
cable/wire or wiring error.
T068
None
Circuit A Return Gas Thermistor Failure
If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F (–40 to 118 C)
None
Automatic Thermistor failure, damaged
cable/wire or wiring error.
T069
None
Circuit B Return Gas Thermistor Failure
If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F –40 to 118 C)
None
Automatic Thermistor failure, damaged
cable/wire or wiring error.
T073
Alert
Outside Air Thermistor
Failure (T9)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Temperature reset
disabled. Chiller runs
under normal control/set
points. When capacity
reaches 0, cooler/pump
heaters are energized.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
T074
Alert
Space Temperature
Thermistor Failure (T10)
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Temperature reset
disabled. Chiller runs
under normal control/set
points.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
T077
Alert
Circuit A Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor
(T1).
Circuit A shutdown after
pumpdown complete.
Automatic Faulty expansion valve or
suction pressure transducer
(T5) or leaving fluid
thermistor (T1).
T078
Alert
Circuit B Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor
(T1).
Circuit B shutdown after
pumpdown complete
Automatic Faulty expansion valve or
suction pressure transducer
(T6) or leaving fluid
thermistor (T1).
T079
Alert
Lead/Lag LWT
Thermistor Failure
Thermistor outside range of
–40 to 245 F (–40 to 118 C)
Chiller runs as a stand
alone machine
Automatic Dual LWT thermistor failure,
damaged cable/wire or
wiring error.
T090
Alert
Circuit A Discharge
Pressure Transducer Failure
Voltage ratio more than
99.9% or less than .5%.
Circuit A shut down
Automatic Transducer failure, poor
connection to MBB, or wiring
damage/error.
T091
Alert
Circuit B Discharge
Pressure Transducer Failure
Voltage ratio more than
99.9% or less than .5%.
Circuit B shut down
Automatic Transducer failure, poor
connection to MBB, or wiring
damage/error.
T092
Alert
Circuit A Suction
Pressure Transducer Failure
Voltage ratio more than
99.9% or less than .5%.
Circuit A shut down
Automatic Transducer failure, poor
connection to MBB, or wiring
damage/error.