Mode – Sterling AquaSnap 30RA010-055 User Manual
Page 70

70
L1
L2
L3
Mode
DANGER
T1
T2
T3
B+
B-
DISPLAY
BUTTONS
Mode
MMV
TERMINAL
BLOCK
1
2
5
6
11
12
2
14
13A
13B
13C
15
25
2
30
31
TXA
TXB
COM
+5V
MMV
TERMINAL
BLOCK
Fig. 38 — Pressure Transducer and Start Command Jumper Wiring
Fig. 37 — Motormaster® V Mode Buttons and Mode Display
*At 208 v, the drive can run in either mode.
MODE
NOMINAL
VOLTAGE
Hz
CONTROL INPUT
(PIN 5)
START
JUMPER
SETPOINT
JUMPER
REFRIGERANT
1
208*/230/
460/575
60
Internal PI control,
0-5V feedback
TB1-TB2
None
R-22
2
208*/230
60
Internal PI control,
0-5V feedback
TB13A-TB2
None
3
230
50
Internal PI control,
0-5V feedback
TB13B-TB2
None
4
380/415
50
Internal PI control,
0-5V feedback
TB13C-TB2
None