Iii. unit start-up (cont) – Sterling AquaSnap 30RA010-055 User Manual
Page 97

CL-5
III. Unit Start-Up (cont)
RECORD CONFIGURATION SETTINGS
UNIT (Configuration Settings)
PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’.
PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:
OPTIONS1 (Options Configuration)
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
UNIT
UNIT CONFIGURATION
SZA.1
XX
COMPRESSOR A1 SIZE
SZA.2
XX
COMPRESSOR A2 SIZE
SZB.1
XX
COMPRESSOR B1 SIZE
SZB.2
XX
COMPRESSOR B2 SIZE
SH.SP
XX.X
∆F
SUPERHEAT SETPOINT
REFG
X
REFRIGERANT
FAN.S
X
FAN STAGING SELECT
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
OPT1
UNIT OPTIONS 1 HARDWARE
FLUD
X
COOLER FLUID
MLV.S
YES/NO
MINIMUM LOAD VALVE SELECT
MMR.S
YES/NO
MOTORMASTER SELECT
RG.EN
ENBL/DSBL
RETURN GAS SENSOR ENABLE
CPC
ON/OFF
COOLER PUMP CONTROL
PM1E
YES/NO
COOLER PUMP 1 ENABLE
PM2E
YES/NO
COOLER PUMP 2 ENABLE
PM.P.S
YES/NO
COOLER PMP PERIODIC STRT
PM.SL
X
COOLER PUMP SELECT
PM.DY
XX MIN
COOLER PUMP SHUTDOWN DLY
PM.DT
XXXX HRS
PUMP CHANGEOVER HOURS
ROT.P
YES/NO
ROTATE COOLER PUMPS NOW
EMM
YES/NO
EMM MODULE INSTALLED