Sterling AquaSnap 30RA010-055 User Manual
Page 79

79
ALARMDEF (Alarm Definition Table)
BRODEFS (Broadcast POC Definition Table)
DISPLAY (Marquee Display SETUP)
DUALCHIL (Dual Chiller Configuration Settings)
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Alarm Routing Control
00000000
00000000
ALRM_CNT
Equipment Priority
0 to 7
4
EQP_TYPE
Comm Failure Retry Time
1 to 240
10
min
RETRY_TM
Re-alarm Time
1 to 255
30
min
RE-ALARM
Alarm System Name
XXXXXXXX
CHILLER
ALRM_NAM
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
SCN Time/Date Broadcast Yes/No No SCNBC
SCN OAT Broadcast Yes/No No OATBC
Global Schedule Broadcast Yes/No No GSBC
SCN Broadcast Ack’er Yes/No No SCNBCACK
Daylight Savings Start:
Month
1 to 12
4
STARTM
Week
1 to 5
1
STARTW
Day
1 to 7
7
STARTD
Minutes to Add
0 to 99
60
min
MINADD
Daylight Savings Stop
Month
1 to 12
10
STOPM
Week
1 to 5
5
STOPW
Day
1 to 7
7
STOPD
Minutes to Subtract
0 to 99
60
min
MINSUB
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Service Password
nnnn
1111
PASSWORD
Password Enable
Enable/Disable
Enable
PASS_EBL
Metric Display
Off/On
Off
DISPUNIT
Language Selection
0 = ENGLISH
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES
0
LANGUAGE
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
LEAD/LAG
Lead/Lag Chiller Enable
Enable/Dsable
Dsable
LL_ENA
Master/Slave Select
Master/Slave
Master
MS_SEL
Slave Address
0 to 239
2
SLV_ADDR
Lead/Lag Balance Select
0 = None
0
LL_BAL
Lead/Lag Balance Delta
40 to 400
168
hours
LL_BAL_D
Lag Start Delay
0 to 30
5
minutes
LL_DELAY
Parallel Configuration
Yes
Yes
PARALLEL