ALARMDEF (Alarm Definition Table)

BRODEFS (Broadcast POC Definition Table)

DISPLAY (Marquee Display SETUP)

DUALCHIL (Dual Chiller Configuration Settings)

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Alarm Routing Control

00000000

00000000

ALRM_CNT

Equipment Priority

0 to 7

4

EQP_TYPE

Comm Failure Retry Time

1 to 240

10

min

RETRY_TM

Re-alarm Time

1 to 255

30

min

RE-ALARM

Alarm System Name

XXXXXXXX

CHILLER

ALRM_NAM

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

SCN Time/Date Broadcast Yes/No No SCNBC
SCN OAT Broadcast Yes/No No OATBC
Global Schedule Broadcast Yes/No No GSBC
SCN Broadcast Ack’er Yes/No No SCNBCACK
Daylight Savings Start:

Month

1 to 12

4

STARTM

Week

1 to 5

1

STARTW

Day

1 to 7

7

STARTD

Minutes to Add

0 to 99

60

min

MINADD

Daylight Savings Stop

Month

1 to 12

10

STOPM

Week

1 to 5

5

STOPW

Day

1 to 7

7

STOPD

Minutes to Subtract

0 to 99

60

min

MINSUB

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Service Password

nnnn

1111

PASSWORD

Password Enable

Enable/Disable

Enable

PASS_EBL

Metric Display

Off/On

Off

DISPUNIT

Language Selection

0 = ENGLISH
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES

0

LANGUAGE

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

LEAD/LAG
Lead/Lag Chiller Enable

Enable/Dsable

Dsable

LL_ENA

Master/Slave Select

Master/Slave

Master

MS_SEL

Slave Address

0 to 239

2

SLV_ADDR

Lead/Lag Balance Select

0 = None

0

LL_BAL

Lead/Lag Balance Delta

40 to 400

168

hours

LL_BAL_D

Lag Start Delay

0 to 30

5

minutes

LL_DELAY

Parallel Configuration

Yes

Yes

PARALLEL