beautypg.com

Sterling AquaSnap 30RA010-055 User Manual

Page 5

background image

5

T10 — REMOTE SPACE TEMPERATURE SENSOR OR
DUAL LEAVING WATER TEMPERATURE SENSOR —
One of two inputs can be connected to TB5-5 and TB5-6. See
appropriate sensor below.
T10 — Remote Space Temperature Sensor — Sensor T10
(part no. 33ZCT55SPT) is an accessory sensor that is remotely
mounted in the controlled space and used for space tempera-
ture reset. The sensor should be installed as a wall-mounted
thermostat would be (in the conditioned space where it will not
be subjected to either a cooling or heating source or direct
exposure to sunlight, and 4 to 5 ft above the floor).

Space temperature sensor wires are to be connected to

terminals in the unit main control box. The space temperature
sensor includes a terminal block (SEN) and a RJ11 female
connector. The RJ11 connector is used access into the Sterlco
Comfort Network (SCN) at the sensor.

To connect the space temperature sensor (Fig. 9):

1. Using a 20 AWG twisted pair conductor cable rated for

the application, connect 1 wire of the twisted pair to one
SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the space
temperature sensor.

2. Connect the other ends of the wires to terminals 5 and 6

on TB5 located in the unit control box.

Units on the SCN can be monitored from the space at the

sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the SCN (Fig. 10):

1. Cut the SCN wire and strip ends of the red (+), white

(ground), and black (–) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)

2. Insert and secure the red (+) wire to terminal 5 of the

space temperature sensor terminal block.

3. Insert and secure the white (ground) wire to terminal 4 of

the space temperature sensor.

4. Insert and secure the black (–) wire to terminal 2 of the

space temperature sensor.

5. Connect the other end of the communication bus cable to

the remainder of the SCN communication bus.

T10 — Dual Leaving Water Temperature Sensor — For
dual chiller applications (parallel only are supported), connect
the dual chiller leaving fluid temperature sensor (5 k

Ω ther-

mistor, Sterling part no. HH79NZ029) to the space temperature
input of the Master chiller. If space temperature is required for
reset applications, connect the sensor to the Slave chiller and
configure the slave chiller to broadcast the value to the Master
chiller.

LEGEND FOR FIG. 1-6

IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the SCN communication bus
wire used for the entire network. Refer to Table 5 for
acceptable wiring.

ALMR

Alarm Relay

BR

Boiler Relay

C

Contactor, Compressor

CB

Circuit Breaker

CCB

Compressor Circuit Breaker

CHC

Cooler/Pump Heater Contactor

COMP

Compressor

CWFS

Chilled Water Flow Switch

CWP

Chilled Water Pump

DPT

Discharge Pressure Transducer

EMM

Energy Management

FIOP

factory Installed Option

FM

Fan Motor

GND

Ground

HPS

High-Pressure Switch

HR

Heat Relay

ICP

Inrush Current Protection

IP

Internal Protection Thermostat

LWT

Leaving Water Temperature

MBB

Main Base Board

MLV

Minimum Load Valve

MS

Manual Starter

OAT

Outdoor-Air Thermistor

OL

Overload

R

Relay

SPT

Suction Pressure Transducer

SW

Switch

T

Thermistor

TB

Terminal Block

TNKR

Storage Tank Heater Relay

TRAN

Transformer

Terminal Block

Terminal (Unmarked)

Terminal (Marked)

Splice

Factory Wiring

Field Wiring

Accessory or Option Wiring

To indicate common potential only;
not to represent wiring.