Iii. unit start-up (cont) – Sterling AquaSnap 30RA010-055 User Manual
Page 98

CL-6
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
OPTIONS2 (Options Configuration)
RSET (Reset Configuration Settings)
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
OPT2
UNIT OPTIONS 2 CONTROLS
CTRL
X
CONTROL METHOD
SCNA XXX SCN ADDRESS
SCNB XXX SCN BUS NUMBER
BAUD X
SCN BAUD RATE
LOAD
X
LOADING SEQUENCE SELECT
LLCS
X
LEAD/LAG CIRCUIT SELECT
LCWT
XX.X
∆F
HIGH LCW ALERT LIMIT
DELY
XX
MINUTES OFF TIME
ICE.M
ENBL/DSBL
ICE MODE ENABLE
CLS.C
ENBL/DSBL
CLOSE CONTROL SELECT
LS.MD
X
LOW SOUND MODE SELECT
LS.ST
00:00
LOW SOUND START TIME
LS.ND
00:00
LOW SOUND END TIME
LS.LT
XXX %
LOW SOUND CAPACITY LIMIT
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
RSET
RESET COOL TEMP
CRST
X
COOLING RESET TYPE
MA.DG
XX.X °F
4-20 - DEGREES RESET
RM.NO
XXX.X °F
REMOTE - NO RESET TEMP
RM.F
XXX.X °F
REMOTE - FULL RESET TEMP
RM.DG
XX.X °F
REMOTE - DEGREES RESET
RT.NO
XXX.X °F
RETURN - NO RESET TEMP
RT.F
XXX.X °F
RETURN - FULL RESET TEMP
RT.DG
XX.X °F
RETURN - DEGREES RESET
DMDC
X
DEMAND LIMIT SELECT
DM20
XXX %
DEMAND LIMIT AT 20 MA
SHNM
XXX
LOADSHED GROUP NUMBER
SHDL
XXX %
LOADSHED DEMAND DELTA
SHTM
XXX
MAXIMUM LOADSHED TIME
DLS1
XXX %
DEMAND LIMIT SWITCH 1
DLS2
XXX %
DEMAND LIMIT SWITCH 2
LLEN
ENBL/DSBL
LEAD/LAG CHILLER ENABLE
MSSL
SLVE/MAST
MASTER/SLAVE SELECT
SLVA
XXX
SLAVE ADDRESS
LLBL
X
LEAD/LAG BALANCE SELECT
LLBD
XXX
LEAD/LAG BALANCE DELTA
LLDY
XXX
LAG START DELAY
PARA
YES/NO
PARALLEL CONFIGURATION