Sterling AquaSnap 30RA010-055 User Manual
Page 81

81
RESETCON (Temperature Reset and Demand Limit)
SCHEDOVR (Timed Override Setup)
SETPOINT
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
COOLING RESET
Cooling Reset Type
0 = No Reset
1 = 4-20 mA input
2 = External temp – OAT
3 = Return Fluid
4 = External temp - SPT
0
CRST_TYP
4-20 MA RESET
4-20 – Degrees Reset
–30 to 30
0.0
∆∆∆∆F
420_DEG
REMOTE RESET
Remote – No Reset Temp
0 to 125
125.0
°°°°F
REM_NO
Remote – Full Reset Temp
0 to 125
0.0
°°°°F
REM_FULL
Remote – Degrees Reset
–30 to 30
0.0
∆∆∆∆F
REM_DEG
RETURN TEMPERATURE RESET
Return – No Reset Temp
0 to 125
10.0
∆∆∆∆F
RTN_NO
Return – Full Reset Temp
0 to 125
0.0
∆∆∆∆F
RTN_FULL
Return – Degrees Reset
–30 to 30
0.0
∆∆∆∆F
RTN_DEG
DEMAND LIMIT
Demand Limit Select
0 = None
1 = External switch input
2 = 4-20 mA input
3 = Loadshed
0
DMD_CTRL
Demand Limit at 20 mA
0 to 100
100
%
DMT20MA
Loadshed Group Number
0 to 99
0
SHED_NUM
Loadshed Demand Delta
0 to 60
0
%
SHED_DEL
Maximum Loadshed Time
0 to 120
60
minutes
SHED_TIM
Demand Limit Switch 1
0 to 100
80
%
DLSWSP1
Demand Limit Switch 2
0 to 100
50
%
DLSWSP2
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Schedule Number
0 to 99
1
SCHEDNUM
Override Time Limit
0 to 4
0
hours
OTL
Timed Override Hours
0 to 4
0
hours
OVR_EXT
Timed Override
No/Yes
No
TIMEOVER
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
COOLING
Cooling Setpoint 1
–20 to 70
44.0
°°°°F
CSP1
Cooling Setpoint 2
–20 to 70
44.0
°°°°F
CSP2
ICE Setpoint
–20 to 32
32.0
°°°°F
CSP3
RAMP LOADING
Cooling Ramp Loading
0.2 to 2.0
1.0
CRAMP
Brine Freeze Point
–20 to 34
34.0
°°°°F
BRN_FRZ