Sterling AquaSnap 30RA010-055 User Manual
Page 80

80
OPTIONS1 (Options 1 Configuration)
OPTIONS2 (Options 2 Configuration)
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Cooler Fluid
1 = Water
2 = Med. Brine
1
FLUIDTYP
Minimum Load Vlv Select
No/Yes
No
MLV_FLG
Return Gas Sensor Enable
Dsable/Enable
Dsable
RGT_ENA
Motormaster Select
No/Yes
No
MTR_TYPE
Cooler Pump Control
Off/On
Off
CPC
Cooler Pump 1 Enable
No/Yes
No
PMP1_ENA
Cooler Pump 2 Enable
Dsable/Enable
Dsable
PMP2_ENA
Cooler Pmp Periodic Strt
No/Yes
No
PUMP_PST
Cooler Pump Select
0 = Automatic
1 = Pump 1
2 = Pump 2
0
PMP_SLCT
Cooler Pump Shutdown Dly
0 to 10
1
minutes
PUMP_DLY
Pump Changeover Hours
10 to 2000
500
hours
PMP_DLTA
EMM Module Installed
No/Yes
No
EMM_BRD
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Control Method
0 = Switch
2 = Occupancy
3 =
SCN
0
CONTROL
Loading Sequence Select
1 = Equal Loading
2 = Staged Loading
1
SEQ_TYP
Lead/Lag Circuit Select
0 = Automatic
1 = Circuit A Leads
2 = Circuit B Leads
0
LEAD_TYP
Cooling Setpoint Select
0 = Single
1 = Dual, remote switch controlled
2 = Dual
SCN occupancy
3 = 4-20 mA input
0
CLSP_TYP
Ramp Load Select
Enable/Dsable
Enable
RAMP_EBL
Heat Cool Select
Cool/Heat
Cool
HEATCOOL
High LCW Alert Limit
2 to 60
60.0
∆∆∆∆F
LCW_LMT
Minutes off time
0 to 15
0
min
DELAY
Deadband Multiplier
1.0 to 4.0
2.0
Z_GAIN
Ice Mode Enable
Enable/Dsable
Dsable
ICE_CNFG
Close Control Select
Enable/Dsable
Dsable
CLS_CTRL
Low Sound Mode Select
0 = Disabled
1 = Fan only
2 = Capacity/Fans
1
LS_MODE
Low Sound Start Time
00:00 to 23:59
00:00
LS_START
Low Sound End Time
00:00 to 23:59
00:00
LS_END
Low Sound Capacity Limit
0 to 100
100
%
LS_LIMIT
Enable Short Loop Gain
Enable/Dsable
Enable
SAGENABL