54 table 29 — alarm and alert codes (cont) – Sterling AquaSnap 30RA010-055 User Manual

Page 54

background image

54

Table 29 — Alarm and Alert Codes (cont)

ALARM/

ALERT

CODE

ALARM

OR

ALERT

DESCRIPTION

WHY WAS THIS

ALARM

GENERATED?

ACTION TAKEN

BY CONTROL

RESET

METHOD

PROBABLE

CAUSE

T093

Alert

Circuit B Suction
Pressure Transducer
Failure

Voltage ratio more than
99.9% or less than .5%.

Circuit B shut down

Automatic

Transducer failure, poor
connection to MBB, or wiring
damage/error.

T110

Alert

Circuit A Loss of Charge

If the compressors are off
and discharge pressure
reading is < 10 psig for
30 sec.

Circuit not allowed to
start.

Manual

Refrigerant leak or
transducer failure

T111

Alert

Circuit B Loss of Charge

If the compressors are off
and discharge pressure
reading is < 10 psig for
30 sec.

Circuit not allowed to
start.

Manual

Refrigerant leak or
transducer failure

T112

Alert

Circuit A High Saturated
Suction Temperature

Circuit saturated suction
temperature pressure
transducer > 60 F (15.6 C)
for 5 minutes

Circuit shut down

Manual

Faulty Expansion valve,
faulty suction pressure
transducer or high entering
fluid temperature.

T113

Alert

Circuit B High Saturated
Suction Temperature

Circuit saturated suction
temperature pressure
transducer > 60 F (15.6 C)
for 5 minutes

Circuit shut down

Manual

Faulty Expansion valve,
faulty suction pressure
transducer or high entering
fluid temperature.

T114

Alert

Circuit A Low Suction
Superheat

Return gas sensor enabled
and suction superheat is
more than 10° F (5.6 C)
below the suction superheat
set point for 5 minutes.

Circuit A shut down after
pumpdown complete.

Automatic restart
after first daily
occurrence.
Manual restart
thereafter.

Faulty expansion valve,
faulty suction pressure
transducer, faulty suction gas
thermistor, circuit
overcharged

T115

Alert

Circuit B Low Suction
Superheat

Return gas sensor enabled
and suction superheat is
more than 10° F (5.6 C)
below the suction superheat
set point for 5 minutes.

Circuit B shut down after
pumpdown complete.

Automatic restart
after first daily
occurrence.
Manual restart
thereafter.

Faulty expansion valve,
faulty suction pressure
transducer, faulty suction
gas thermistor, circuit
overcharged

T116

Alert

Circuit A Low Cooler
Suction Temperature

Mode 7 caused the com-
pressor to unload 6 consecu-
tive times with less than a
30-minute interval between
each circuit shutdown.

Circuit shut down

Manual

Faulty expansion valve, low
refrigerant charge, plugged
filter drier, faulty suction
pressure transducer, low
cooler fluid flow

T117

Alert

Circuit B Low Cooler
Suction Temperature

Mode 8 caused the com-
pressor to unload 6 consecu-
tive times with less than a
30-minute interval between
each circuit shutdown.

Circuit shut down

Manual

Faulty expansion valve, low
refrigerant charge, plugged
filter drier, faulty suction
pressure transducer, low
cooler fluid flow

T126

Alert

Circuit A High
Discharge Pressure

SCT >Maximum condensing
temperature from operating
envelope

Circuit shut down

Automatic, only
after first 3 daily
occurrences.
Manual reset
thereafter. Read-
ing from OAT sen-
sor (T9) must drop
5 F (2.8 C) before
restart

Faulty transducer/high
pressure switch, low/
restricted condenser
airflow

T127

Alert

Circuit B High
Discharge Pressure

SCT >Maximum condensing
temperature from operating
envelope

Circuit shut down

Automatic, only
after first 3 daily
occurrences. Man-
ual reset thereafter.
Reading from OAT
sensor (T9) must
drop 5 F (2.8 C)
before restart

Faulty transducer/high
pressure switch, low/
restricted condenser
airflow

T133

Alert

Circuit A Low Suction
Pressure

Suction pressure below
15 psig for 8 seconds or
below 8 psig

Circuit shut down

Automatic
restart after first
daily occurrence.
Manual restart
thereafter.

Faulty or plugged TXV, low
refrigerant charge, TXV out
of adjustment, liquid
line valve partially closed

T134

Alert

Circuit B Low Suction
Pressure

Suction pressure below
15 psig for 8 seconds or
below 8 psig

Circuit shut down

Automatic
restart after first
daily occurrence.
Manual restart
thereafter.

Faulty or plugged TXV, low
refrigerant charge, TXV out
of adjustment, liquid
line valve partially closed