III. Unit Start-Up (cont)

COMPONENT TEST

USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’.
PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT
‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO
RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY
AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE
BELOW.

Service Test Mode and Sub-Mode Directory

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.

SUB-MODE

KEYPAD

ENTRY

ITEM DISPLAY

ITEM

EXPANSION

COMMENT

Completed

(Yes/No)

TEST

ON/OFF

SERVICE TEST MODE

To Enable Service Test Mode,
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.

OUTS

OUTPUTS AND PUMPS

FAN1

ON/OFF

FAN 1 RELAY

SIZES 010-018,
Condenser fan at low speed
SIZES 022-030
Condenser fan A1 energized
SIZES 032-055,
Condenser fan A2 energized

FAN2

ON/OFF

FAN 2 RELAY

SIZES 022-030,
Condenser fan A2 energized
SIZES 032-040,
Condenser fan B1 at high speed
SIZES 042-055,
Condenser fan B2 energized

CLP.1

ON/OFF

COOLER PUMP 1 RELAY

CLP.2

ON/OFF

COOLER PUMP 2 RELAY

CL.HT

ON/OFF

COOLER/PUMP HEATER

RMT.A

ON/OFF

REMOTE ALARM RELAY

CMPA

CIRCUIT A COMPRESSOR TEST

CC.A1

ON/OFF

COMPRESSOR A1 RELAY

CC.A2

ON/OFF

COMPRESSOR A2 RELAY

MLV

ON/OFF

MINIMUM LOAD VALVE RELAY

CMPB

CIRCUIT B COMPRESSOR TEST

CC.B1

ON/OFF

COMPRESSOR B1 RELAY

See Note

CC.B2

ON/OFF

COMPRESSOR B2 RELAY

See Note

MLV

ON/OFF

MINIMUM LOAD VALVE RELAY

See Note

ENTER

ENTER

ENTER

ENTER