Table 29 — Alarm and Alert Codes (cont)

LEGEND

ALARM/

ALERT

CODE

ALARM

OR

ALERT

DESCRIPTION

WHY WAS THIS

ALARM

GENERATED?

ACTION TAKEN

BY CONTROL

RESET

METHOD

PROBABLE

CAUSE

T301

Alert

Cooler Pump 2
Scheduled
Maintenance Due

Pump 2 Service
Countdown (P.2.DN)
expired. Complete pump 2
maintenance and
enter 'YES' for Pump 1
Maintenance Done
(P.2.MN) item.

None

Automatic

Routine pump
maintenance
required

T302

Alert

Strainer Blowdown
Scheduled
Maintenance Due

Strainer Service
Countdown (S.T.DN)
expired. Complete strainer
blowdown and enter 'YES' for
Strainer Maintenance Done
(S.T.MN) item.

None

Automatic

Routine strainer
maintenance
required

T303

Alert

Condenser Coil
Maintenance Due

Coil Service Countdown
(C.L.DN) expired.
Complete condenser coil
cleaning and enter 'YES'
for Coil Maintenance Done
(C.L.MN) item.

None

Automatic

Routine condenser
coil maintenance
required

T950

Alert

Loss of Communication
with Water System
Manager

No communications have
been received by the MBB
within 5 minutes of last
transmission

WSM forces removed.
Chiller runs under own
control

Automatic

Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address

T951

Alert

Loss of Communication
with Flotronic™ System
Manager

No communications have
been received by the MBB
within 5 minutes of last
transmission

FSM forces removed.
Chiller runs under own
control

Automatic

Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address

T952

Alert

Loss of Communication
with Hydronic System
Manager

No communications have
been received by the MBB
within 5 minutes of last
transmission

HSM forces removed.
Chiller runs under own
control

Automatic

Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address

SCN — Sterlco Comfort Network
EMM

Energy Management Module

EWT

Entering Fluid Temperature

FSM

Flotronic™ System Manager

HSM

Hydronic System Manager

LCW

Leaving Chilled Water

LWT

Leaving Fluid Temperature

MBB

Main Base Board

OAT

Outdoor-Air Temperature

SCT

Saturated Condensing Temperature

TXV

Thermostatic Expansion Valve

WSM — Water System Manager