Sterling AquaSnap 30RA010-055 User Manual
Page 33

33
Table 17 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
RSET (cont)
RM.F
XXX.X
°F
REMOTE - FULL RESET TEMP
Default: 0.0
° F (-17.8 C)
Range: 0
° to 125 F
RM.DG
XX.X
°F
REMOTE - DEGREES RESET
Default: 0.0
° F
Range: –30 to 30
F
RT.NO
XXX.X
∆F
RETURN - NO RESET TEMP
Default: 10.0
∆F (5.6 ∆C)
Range: 0
° to 125 F COOLER ∆T
RT.F
XXX.X
∆F
RETURN - FULL RESET TEMP
Default: 0.0
∆F (0.0 ∆C)
Range: 0
° to 125 F COOLER ∆T
RT.DG
XX.X
°F
RETURN - DEGREES RESET
Default: 0.0
° F
Range: –30 to 30
F (–34.4 to -1.1 C)
DMDC
X
DEMAND LIMIT SELECT
Default: None
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 =
SCN Loadshed
DM20
XXX %
DEMAND LIMIT AT 20 MA
Default: 100%
Range: 0 to 100%
SHNM
XXX
LOADSHED GROUP NUMBER
Default: 0
Range: 0 to 99
SHDL
XXX %
LOADSHED DEMAND DELTA
Default: 0%
Range: 0 to 60%
SHTM
XXX
MAXIMUM LOADSHED TIME
Default: 60 minutes
Range: 0 to 120 minutes
DLS1
XXX %
DEMAND LIMIT SWITCH 1
Default: 80%
Range: 0 to 100%
DLS2
XXX %
DEMAND LIMIT SWITCH 2
Default: 50%
Range: 0 to 100%
LLEN
ENBL/DSBL
LEAD/LAG CHILLER ENABLE
Default: Disable
MSSL
SLVE/MAST
MASTER/SLAVE SELECT
Default: Master
SLVA
XXX
SLAVE ADDRESS
Default: 2
Range: 0 to 239
LLBL
X
LEAD/LAG BALANCE SELECT
Default: Master Leads
0 = Master Leads
1 = Slave Leads
2 = Automatic
LLBD
XXX
LEAD/LAG BALANCE DELTA
Default: 168 hours
Range: 40 to 400 hours
LLDY
XXX
LAG START DELAY
Default: 5 minutes
Range: 0 to 30 minutes
PARA
YES
PARALLEL CONFIGURATION
Default: YES (CANNOT BE CHANGED)
SLCT
SETPOINT AND RAMP LOAD
CLSP
X
COOLING SETPOINT SELECT
Default: Single
0 = Single
1 = Dual Switch
2 = Dual
SCN Occupied
3 = 4 to 20 mA Input (requires
EMM)
RL.S
ENBL/DSBL
RAMP LOAD SELECT
Default: Enable
CRMP
X.X
COOLING RAMP LOADING
Default: 1.0
Range: 0.2 to 2.0
SCHD
XX
SCHEDULE NUMBER
Default: 1
Range: 1 to 99
Z.GN
X.X
DEADBAND MULTIPLIER
Default: 2.0
Range: 1.0 to 4.0
SERV
SERVICE CONFIGURATION
EN.A1
ENBL/DSBL
ENABLE COMPRESSOR A1
Unit dependent
EN.A2
ENBL/DSBL
ENABLE COMPRESSOR A2
Unit dependent
EN.B1
ENBL/DSBL
ENABLE COMPRESSOR B1
Unit dependent
EN.B2
ENBL/DSBL
ENABLE COMPRESSOR B2
Unit dependent
BCST
BROADCAST CONFIGURATION
T.D.BC ON/OFF
SCN TIME/DATE BROADCAST
OAT.B ON/OFF
SCN OAT BROADCAST
G.S.BC ON/OFF GLOBAL SCHEDULE BROADCAST
BC.AK ON/OFF
SCN BROADCAST ACK’ER
ENTER
ENTER
ENTER
ENTER