Table 12 — temperature mode and sub-mode directory – Sterling AquaSnap 30RA010-055 User Manual
Page 29

29
Table 11 — Service Test Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 12 — Temperature Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
TEST
ON/OFF
SERVICE TEST MODE
To Enable Service Test Mode,
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
OUTS
OUTPUTS AND PUMPS
FAN1
ON/OFF
FAN 1 RELAY
FAN2
ON/OFF
FAN 2 RELAY
CLP.1
ON/OFF
COOLER PUMP 1 RELAY
CLP.2
ON/OFF
COOLER PUMP 2 RELAY
CL.HT
ON/OFF
COOLER/PUMP HEATER
RMT.A
ON/OFF
REMOTE ALARM RELAY
CMPA
CIRCUIT A COMPRESSOR TEST
CC.A1
ON/OFF
COMPRESSOR A1 RELAY
CC.A2
ON/OFF
COMPRESSOR A2 RELAY
MLV
ON/OFF
MINIMUM LOAD VALVE RELAY
CMPB
CIRCUIT B COMPRESSOR TEST
See Note
CC.B1
ON/OFF
COMPRESSOR B1 RELAY
CC.B2
ON/OFF
COMPRESSOR B2 RELAY
MLV
ON/OFF
MINIMUM LOAD VALVE RELAY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
UNIT
ENT AND LEAVE UNIT TEMPS
CEWT
XXX.X
°F
COOLER ENTERING FLUID
CLWT
XXX.X
°F
COOLER LEAVING FLUID
OAT
XXX.X
°F
OUTSIDE AIR TEMPERATURE
SPT
XXX.X
°F
SPACE TEMPERATURE
DLWT
XXX.X
°F
LEAD/LAG LEAVING FLUID
CIR.A
TEMPERATURES CIRCUIT A
SCT.A
XXX.X
°F
SATURATED CONDENSING TMP
SST.A
XXX.X
°F
SATURATED SUCTION TEMP
RGT.A
XXX.X
°F
COMPR RETURN GAS TEMP
SH.A
XXX.X ^F
SUCTION SUPERHEAT TEMP
CIR.B
TEMPERATURES CIRCUIT B
See Note
SCT.B
XXX.X
°F
SATURATED CONDENSING TMP
See Note
SST.B
XXX.X
°F
SATURATED SUCTION TEMP
See Note
RGT.B
XXX.X
°F
COMPR RETURN GAS TEMP
See Note
SH.B
XXX.X ^F
SUCTION SUPERHEAT TEMP
See Note
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER