30 table 13 — pressure mode and sub-mode directory – Sterling AquaSnap 30RA010-055 User Manual
Page 30

30
Table 13 — Pressure Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 14 — Set Point and Sub-Mode Directory
Table 15 — Inputs Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
PRC.A
PRESSURES CIRCUIT A
DP.A
XXX.X PSIG
DISCHARGE PRESSURE
SP.A
XXX.X PSIG
SUCTION PRESSURE
PRC.B
PRESSURES CIRCUIT B
See Note
DP.B
XXX.X PSIG
DISCHARGE PRESSURE
See Note
SP.B
XXX.X PSIG
SUCTION PRESSURE
See Note
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
COOL
COOLING SETPOINTS
CSP.1
XXX.X
°F
COOLING SETPOINT 1
Default: 44 F
CSP.2
XXX.X
°F
COOLING SETPOINT 2
Default: 44 F
CSP.3
XXX.X
°F
ICE SETPOINT
Default: 32 F
HEAD
HEAD PRESSURE SETPOINTS
HD.P.A
XXX.X
°F
CALCULATED HP SETPOINT A
Default: 113 F
(Read Only)
HD.P.B
XXX.X
°F
CALCULATED HP SETPOINT B
Default: 113 F
(Read Only)
FRZ
BRINE FREEZE SETPOINT
BR.FZ
XXX.X
°F
BRINE FREEZE POINT
Default: 34 F
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
GEN.I
GENERAL INPUTS
STST
STRT/STOP
START/STOP SWITCH
FLOW
ON/OFF
COOLER FLOW SWITCH
PM.F.1
OPEN/CLSE
COOLER PUMP 1 INTERLOCK
LD.PM
X
Lead Pump
1 = Pump 1
2 = Pump 2
3 = No Pump
PM.F.2
OPEN/CLSE
COOLER PUMP 2 INTERLOCK
HT.RQ
ON/OFF
HEAT REQUEST
DLS1
ON/OFF
DEMAND LIMIT SWITCH 1
DLS2
ON/OFF
DEMAND LIMIT SWITCH 2
ICED
ON/OFF
ICE DONE
DUAL
ON/OFF
DUAL SETPOINT SWITCH
CRCT
CIRCUITS INPUTS
FKA1 ON/OFF
COMPRESSOR
A1
FEEDBACK
FKA2 ON/OFF
COMPRESSOR
A2
FEEDBACK
FKB1
ON/OFF
COMPRESSOR B1 FEEDBACK
See Note
FKB2
ON/OFF
COMPRESSOR B2 FEEDBACK
See Note
4-20
4-20 MA INPUTS
DMND
XX.X MA
4-20 MA DEMAND SIGNAL
RSET
XX.X MA
4-20 MA RESET SIGNAL
CSP
XX.X MA
4-20 MA COOLING SETPOINT
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER