CURRMODS: Maintenance Display
DUALCHIL: Maintenance Display
DESCRIPTION
VALUE
POINT NAME
FSM controlling Chiller
On/Off
MODE_1
WSM controlling Chiller
On/Off
MODE_2
Master/Slave control
On/Off
MODE_3
Ramp Load Limited
On/Off
MODE_5
Timed Override in effect
On/Off
MODE_6
Low Cooler Suction TempA
On/Off
MODE_7
Low Cooler Suction TempB
On/Off
MODE_8
Slow Change Override
On/Off
MODE_9
Minimum OFF time active
On/Off
MODE_10
Dual Setpoint
On/Off
MODE_13
Temperature Reset
On/Off
MODE_14
Demand/Sound Limited
On/Off
MODE_15
Cooler Freeze Protection
On/Off
MODE_16
Low Temperature Cooling
On/Off
MODE_17
High Temperature Cooling
On/Off
MODE_18
Making ICE
On/Off
MODE_19
Storing ICE
On/Off
MODE_20
High SCT Circuit A
On/Off
MODE_21
High SCT Circuit B
On/Off
MODE_22
Minimum Comp. On Time
On/Off
MODE_23
Pump Off Delay Time
On/Off
MODE_24
Low Sound Mode
On/Off
MODE_25
Short Loop Override
On/Off
MODE_26
DESCRIPTION
VALUE
UNITS
POINT NAME
Dual Chiller Link Good?
Yes/No
DC_LINK
Master Chiller Role
Stand Alone,
Lead Chiller,
Lag Chiller
MC_ROLE
Slave Chiller Role
Stand Alone,
Lead Chiller,
Lag Chiller
SC_ROLE
Lead Chiller Ctrl Point
snnn.n
°°°°F
LEAD_CP
Lag Chiller Ctrl Point
snnn.n
°°°°F
LAG_CP
Control Point
snnn.n
°°°°F
CTRL_PNT
Cool EnteringFluid-Slave
snnn.n
°°°°F
COOLEWTS
Cool Leaving Fluid-Slave
snnn.n
°°°°F
COOLLWTS
Cooler Entering Fluid
snnn.n
°°°°F
COOL_EWT
Cooler Leaving Fluid
snnn.n
°°°°F
COOL_LWT
Lead/Lag Leaving Fluid
snnn.n
°°°°F
DUAL_LWT
Percent Avail.Capacity
0-100
%
CAP_A
Percent Avail.Cap.Slave
0-100
%
CAP_A_S
Lag Start Delay Time
hh:mm
LAGDELAY
Load/Unload Factor
snnn.n
SMZ
Load/Unload Factor-Slave
snnn.n
SMZSLAVE
Lead SMZ Clear Commanded
Yes/No
LEADSMZC
Lag- SMZ Clear Commanded
Yes/No
LAG_SMZC
Lag Commanded Off?
Yes/No
LAG_OFF
Dual Chill Lead CapLimit
0-100
%
DCLDCAPL
Dual Chill Lag CapLimit
0-100
%
DCLGCAPL