Table 22 — Dual Chiller Configuration (Slave Chiller Example)
NOTES:
1. Slave Control Method (CTRL) must be configured for 0.
2. Slave
SCN Address (SCNA) must be different than Master.
3. Slave
SCN Bus Number (SCNB) must be the same as Master
4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.
SUB-MODE
ITEM
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENTS
DISP
UNIT
OPT1
OPT2
CTRL
CONTROL METHOD
CTRL
0
SWITCH
DEFAULT 0
CTRL
CTRL
SCNA
SCNA 1 SCN ADDRESS SCROLLING STOPS
1 VALUE FLASHES
2
SELECT 2
(SEE NOTE 1)
SCNA 2 SCN ADDRESS CHANGE ACCEPTED
SCNA
SCNB
SCNB 0 SCN BUS NUMBER DEFAULT 0
(SEE NOTE 2)
SCNB
OPT2
RSET
PROCEED TO
SUBMODE RSET
RSET
CRST
COOLING RESET TYPE
LLEN
LEAD/LAG CHILLER ENABLE
15 ITEMS
LLEN
DSBL
SCROLLING STOPS
DSBL
VALUE FLASHES
ENBL
SELECT ENBL
LLEN
ENBL
LEAD/LAG CHILLER ENABLE
CHANGE ACCEPTED
LLEN
MSSL
MASTER /SLAVE SELECT
MSSL
MAST
SCROLLING STOPS
MAST
VALUE FLASHES
SLVE
SELECT SLVE
MSSL
SLVE
MASTER /SLAVE SELECT
CHANGE ACCEPTED
MSSL
RSET
SLAVE COMPLETE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ESCAPE