Table 29 — Alarm and Alert Codes (cont)

ALARM/

ALERT

CODE

ALARM

OR

ALERT

DESCRIPTION

WHY WAS THIS

ALARM

GENERATED?

ACTION TAKEN

BY CONTROL

RESET

METHOD

PROBABLE

CAUSE

A140

Alert

Reverse Rotation
Detected

Incoming chiller power
leads not phased correctly

Chiller not allowed to
start.

Manual

Reverse any two
incoming power
leads to correct.
Check for correct fan
rotation first.

A150 Alarm Emergency Stop

SCN emergency stop
command received

Chiller shutdown
without going through
pumpdown.

Automatic once

SCN

command for
EMSTOP returns to
normal

SCN Network
command.

A151

Alarm

Illegal Configuration

One or more illegal
configurations exists.

Chiller is not allowed to
start.

Manual once
configuration errors
are corrected

Configuration error.
Check unit settings.

A152

Alarm

Unit Down Due to
Failure

Both circuits are down due
to alarms/alerts.

Chiller is unable
to run.

Automatic once
alarms/alerts are
cleared that prevent
the chiller from
starting.

Alarm notifies user
that chiller is 100%
down.

T153

Alert

Real Time Clock
Hardware Failure

Internal clock on MBB fails

Occupancy schedule
will not be used. Chiller
defaults to Local On
mode.

Automatic when
correct clock control
restarts.

Time/Date/Month/
Day/Year not
properly set.

A154

Alarm

Serial EEPROM
Hardware Failure

Hardware failure with MBB

Chiller is unable
to run.

Manual

Main Base Board
failure.

T155

Alert

Serial EEPROM
Storage Failure

Configuration/storage
failure with MBB

No Action

Manual

Potential failure of
MBB. Download
current operating
software. Replace
MBB if error occurs
again.

A156

Alarm

Critical Serial EEPROM
Storage Failure

Configuration/storage
failure with MBB

Chiller is not allowed
to run.

Manual

Main Base Board
failure.

A157

Alarm

A/D Hardware Failure

Hardware failure with
peripheral device

Chiller is not allowed
to run.

Manual

Main Base Board
failure.

A189

Alarm

Cooler pump auxiliary
contact inputs miswired

Pump 1 (2) aux contacts
closed when pump 2 (1)
energized.

Both pump outputs
are turned off.

Manual

Wiring error, faulty
pump contactor
auxiliary contacts.

T173

Alert

Loss of Communication
with EMM

MBB loses communication
with EMM

4 to 20 mA
temperature reset
disabled. Demand
Limit set to 100%. 4 to
20 mA set point
disabled.

Automatic

Wiring error, faulty
wiring or failed
Energy Manage-
ment Module (EMM).

T174

Alert

4 to 20 mA Cooling Set
Point Input Failure

If configured with EMM and
input less than 2 mA or
greater than 22 mA

Set point function
disabled. Chiller
controls to CSP1.

Automatic

Faulty signal
generator, wiring
error, or faulty EMM.

T176

Alert

4 to 20 mA
Temperature Reset
Input Failure

If configured with EMM
and input less than 2 mA or
greater than 22 mA

Reset function
disabled. Chiller
returns to normal set
point control.

Automatic

Faulty signal
generator, wiring
error, or faulty EMM.

T177

Alert

4 to 20 mA Demand
Limit Input Failure

If configured with EMM and
input less than 2 mA or
greater than 22 mA

Demand limit function
disabled. Chiller
returns to 100%
demand limit
control.

Automatic

Faulty signal
generator, wiring
error, or faulty EMM.

T189

Alarm

Cooler pump 2 and
Aux Contact Input
miswired

Alarm is generated when
the pump’s aux contacts
close when a pump is
called for

Chiller not allowed to
start

Manual

Wiring error

T190

Alert

Cooler pump 1 Aux
Contacts Failed to Close
at Start-Up

Pump 1 Auxiliary Contacts
did not close within
26 seconds after pump
was started

Pump 1 turned off.
Pump 2 will be started
if available.

Manual

Wiring error, faulty
contacts on pump
contactor

T191

Alert

Cooler pump 2 Aux
Contacts Failed to Close
at Start-Up

Pump 2 Auxiliary Contacts
did not close within
26 seconds after pump
was started

Pump 2 turned off.
Pump 1 will be started
if available.

Manual

Wiring error, faulty
contacts on pump
contactor

T192

Alert

Cooler pump 1 Failed
to Provide Flow at
Start-Up

Pump 1 did not provide
flow to close flow switch
within 60 seconds

Pump 1 turned off.
Pump 2 will be started
if available.

Manual

Wiring error, pump
circuit breaker
tripped, contactor
failure

T193

Alert

Cooler pump 2 Failed
to Provide Flow at
Start-Up

Pump 2 did not provide
flow to close flow switch
within 60 seconds

Pump 1 turned off.
Pump 2 will be started
if available.

Manual

Wiring error, pump
circuit breaker
tripped, contactor
failure

T194

Alert

Cooler pump 1 Aux
Contacts Opened
During Normal
Operation

Pump 1 Auxiliary Contacts
open for 26 seconds after
initially made. All
compressors shut down.
Pump 1 turned off.

Pump 2 will be started
if available. Chiller
allowed to run if
Pump 2 successfully
starts.

Manual

Wiring error, faulty
contacts on pump
contactor

T195

Alert

Cooler pump 2 Aux
Contacts Opened
During Normal
Operation

Pump 2 Auxiliary Contacts
open for 26 seconds after
initially made. All
compressors shut down.
Pump 2 turned off.

Pump 1 will be started
if available. Chiller
allowed to run if
Pump 1 successfully
starts.

Manual

Wiring error, faulty
contacts on pump
contactor