Monitoring temperatures of modules, Monitoring temperatures of modules -10 – Juniper Networks ERX-1410 User Manual
Page 116

CHAPTER 8
Troubleshooting
8-10
Monitoring Temperatures of Modules
You can view the temperature of each module by issuing the
show
environment all and show environment table commands. In
addition, the system generates detailed log messages if the temperature of
a module is outside normal operating limits.
If the temperature of any module exceeds the upper temperature limit,
the system immediately goes into thermal protection mode. Once the
system has entered thermal protection mode, you must resolve the cause
of the high temperature.
When you have resolved the cause of the high temperature, you must
power cycle the system to reset the modules.
Table 8-5 Redundancy status of a line module
ONLINE LED
REDUNDANT LED State of the Line Module
Off
Off
Module is booting or is an inactive primary line
module.
On
Off
Module is active, but no standby module is
available.
Off
On
Module is in standby state.
On
On
Module is active, and a standby module is
available.
Table 8-6 Troubleshooting high-temperature conditions
Cause of High Operating
Temperature
Symptoms
Resolution
Air vents to system are blocked
Space around system does not meet
specifications (see
Increase space around system.
Ambient temperature exceeds
specifications
Ambient temperature exceeds
specifications (see
Provide extra cooling or heating in
the room where the system is
located.
Cooling fan failure
•
FAN OK LED on SRP module is
not illuminated.
•
FAN FAIL LED on SRP module is
illuminated.
Replace fan tray (see
Module failure
FAIL LED on module is illuminated.
Replace module (see