Harmonic suppression guideline

Harmonic currents flow from the inverter to a power
receiving point via a power transformer.The harmonic
suppression guidelines were established to protect other
consumers from these outgoing harmonic currents.
The three-phase 200V input specifications 3.7kW or less
are previously covered by "Harmonic suppression
guideline for household appliances and general-purpose
products" and other models are covered by "Harmonic
suppression guideline for consumers who receive high
voltage or special high voltage". However, the general-
purpose inverter has been excluded from the target
products covered by "Harmonic suppression guideline for
household appliances and general-purpose products" in
January 2004 and all capacities of all models are now
target products of "Harmonic suppression guideline for
consumers who receive high voltage or special high
voltage".
⋅ Harmonic suppression guideline for consumers who

receive high voltage or special high voltage

This guideline sets forth the maximum values of
harmonic currents outgoing from a high-voltage or
especially high-voltage consumer who will install,
add or renew harmonic generating equipment. If any
of the maximum values is exceeded, this guideline
requires that consumer to take certain suppression
measures.

Users who use models other than the target models are
not covered by the guideline. However, we ask to connect
an AC reactor and a DC reactor as before.

For compliance to the "Harmonic suppression guideline
for consumers who receive high voltage or special high
voltage"

For compliance to "Harmonic suppression guideline of
the general-purpose inverter (input current of 20A or less)
for consumers other than specific consumers" published
by JEMA

Calculation of outgoing harmonic current

Input

Power

Supply

Target

Capacity

Measures

Three-

phase 200V

All

capacities

Make a judgment based on "Harmonic
suppression guideline for consumers who receive
high voltage or special high voltage" issued by the
Japanese Ministry of Economy, Trade and Industry
(formerly Ministry of International Trade and
Industry) in September 1994 and take measures if
necessary. For calculation method of power supply
harmonics, refer to materials below.

Reference materials
⋅ "Harmonic suppression measures of the

general-purpose inverter"
Jan., 2004 Japan Electrical Manufacturer's
Association

⋅ "Calculation method of harmonic current of the

general-purpose inverter used by specific
consumers"
JEM-TR201 (Revised in December 2003) :
Japan Electrical Manufacturer's Association

Three-

phase 400V

Input

Power

Supply

Target

Capacity

Measures

Three-

phase 200V

3.7kW

or less

Connect the AC reactor or DC reactor
recommended in a catalog or an instruction manual.

Reference materials
⋅ "Harmonic suppression guideline of the general-

purpose inverter (input current of 20A or less)"
JEM-TR226 (Revised in December 2003) :
Japan Electrical Manufacturer's Association

Outgoing harmonic current = fundamental wave current (value converterd from
received power voltage)

× operation ratio × harmonic content

⋅ Operation ratio: Operation ratio = actual load factor × operation time ratio

during 30 minutes

⋅ Harmonic content: Found in Table.

Table 1: Harmonic content (Values of the fundamental current is 100%)

Reactor

5th

7th

11th

13th

17th

19th

23rd

25th

Not used

65

41

8.5

7.7

4.3

3.1

2.6

1.8

Used (AC side)

38

14.5

7.4

3.4

3.2

1.9

1.7

1.3

Used (DC side)

30

13

8.4

5.0

4.7

3.2

3.0

2.2

Used (AC, DC sides)

28

9.1

7.2

4.1

3.2

2.4

1.6

1.4

Table 2: Rated capacities and outgoing harmonic currents of inverter-driven motors

Applied

Motor

kW

Rated

Current [A]

Fundamen

tal Wave

Current

Converted
from 6.6kV

(mA)

Rated

Capacity

(kVA)

Fundamental Wave Current Converted from

6.6kV

(No reactor, 100% operation ratio)

200V 400V

5th

7th 11th 13th 17th 19th 23rd 25th

0.75

2.74 1.37

83

0.97

53.95 34.03 7.055 6.391 3.569 2.573 2.158 1.494

1.5

5.50 2.75

167

1.95

108.6 68.47 14.20 12.86 7.181 5.177 4.342 3.006

2.2

7.93 3.96

240

2.81

156.0 98.40 20.40 18.48 10.32 7.440 6.240 4.320

3.7

13.0 6.50

394

4.61

256.1 161.5 33.49 30.34 16.94 12.21 10.24 7.092

5.5

19.1 9.55

579

6.77

376.4 237.4 49.22 44.58 24.90 17.95 15.05 10.42

7.5

25.6 12.8

776

9.07

504.4 318.2 65.96 59.75 33.37 24.06 20.18 13.97

11

36.9 18.5

1121

13.1

728.7 459.6 95.29 86.32 48.20 34.75 29.15 20.18

15

49.8 24.9

1509

17.6

980.9 618.7 128.3 116.2 64.89 46.78 39.24 27.16

18.5

61.4 30.7

1860

21.8

1209 762.6 158.1 143.2 79.98 57.66 48.36 33.48

22

73.1 36.6

2220

25.9

1443 910.2 188.7 170.9 95.46 68.82 57.72 39.96

30

98.0 49.0

2970

34.7

1931 1218 252.5 228.7 127.7 92.07 77.22 53.46

37

121 60.4

3660

42.8

2379 1501 311.1 281.8 157.4 113.5 95.16 65.88

45

147 73.5

4450

52.1

2893 1825 378.3 342.7 191.4 138.0 115.7 80.10

55

180 89.9

5450

63.7

3543 2235 463.3 419.7 234.4 169.0 141.7 98.10

Applied

Motor

kW

Rated

Current [A]

Fundamen

tal Wave

Current

Converted
from 6.6kV

(mA)

Rated

Capacity

(kVA)

Fundamental Wave Current Converted from

6.6kV

(With DC reactor , 100% operation ratio)

200V 400V

5th

7th 11th 13th 17th 19th 23rd 25th

75

245 123

8200

87.2

2237 969 626 373 350 239 224 164

90

293 147

9800

104

2673 1158 748 445 419 285 267 196

110

357 179

11933

127

3254 1410 911 542 510 347 325 239

132

216

14400

153

3927 1702 1100 655 615 419 393 288

160

258

17200

183

4691 2033 1313 782 735 500 469 344

220

355

23667

252

6455 2797 1807 1076 1011 688 645 473

250

403

26867

286

7327 3175 2052 1221 1148 782 733 537

280

450

27273

319

8182 3545 2291 1364 1282 873 818 600

315

506

30667

359

9200 3987 2576 1533 1441 981 920 675

355

571

34606

405

10382 4499 2907 1730 1627 1107 1038 761

400

643

38970

456

11691 5066 3274 1949 1832 1247 1169 857

450

723

43818

512

13146 5696 3681 2191 2060 1402 1315 964

500

804

48727

570

14618 6335 4093 2436 2290 1559 1462 1072

560

900

54545

638

16364 7091 4582 2727 2564 1746 1636 1200