Pr.

Pr.

You can switch the display language of the parameter unit (FR-
PU04) to another.

The output current during inverter running can be detected and
output to the output terminal.

(1) Output current detection

(Y12 signal, Pr. 150, Pr. 151, Pr. 166, Pr. 167)

⋅ The output current detection function can be used for

excessive torque detection, etc.

⋅ If the output current remains higher than the Pr. 150 setting

during inverter operation for longer than the time set in Pr.
151
, the output current detection signal (Y12) is output from
the inverter's open collector or relay output terminal.

(2) Zero current detection (Y13 signal, Pr. 152, Pr. 153)

⋅ If the output current remains lower than the Pr. 152 setting

during inverter operation for longer than the time set in Pr.
153
, the zero current detection (Y13) signal is output from
the inverter's open collector or relay output terminal.

You can select the second function using the external terminal
(RT signal).
You can also set the RT signal operation condition (reflection time).

⋅ Functions that can be set as second functions

Parameter which can be read from the operation panel and parameter
unit can be restricted.
In the initial setting, only the simple mode parameters are displayed.

(1) Display of simple mode parameters and extended

parameters (Pr.160)

⋅ When Pr. 160 = "9999" (initial value), only the simple mode

parameters can be displayed on the operation panel (FR-
DU07) and parameter unit (FR-PU04).

⋅ When “0” is set in Pr. 160, simple mode parameters and

extended parameters can be displayed.

(2) User group function (Pr.160, Pr.172 to Pr.174)

⋅ The user group function is designed to display only the

parameters necessary for setting.

⋅ From among all parameters, a maximum of 16 parameters can

be registered to a user group. When Pr. 160 is set in "1", only the
parameters registered to the user group can be accessed. (The
parameters not registered to the user group cannot be read.)

⋅ To register a parameter to the user group, set its parameter

number to Pr. 173.

⋅ To delete a parameter from the user group, set its parameter

number to Pr. 174. To batch-delete the registered parameters, set
Pr. 172 in "9999".

Parameter unit display language
selection

Pr.145 PU display language selection

Pr.145 Setting

Description

0 (initial value)

Japanese

1

English

2

German

3

French

4

Spanish

5

Italian

6

Swedish

7

Finnish

148, 149

Refer to the section about Pr. 22 and
other relevant parameters.

Detection of output current (Y12 signal) detection
of zero current (Y13 signal)

Pr.150 Output current detection level

Pr.151 Output current detection signal delay time

Pr.152 Zero current detection level

Pr.153 Zero current detection time

Pr.166 Output current detection signal retention time
Pr.167 Output current detection operation selection

154

Refer to the section about Pr. 22 and other

relevant parameters.

Pr.

145

Pr.

Pr.

150 to 153, 166, 167

Time

Pr.150

OFF

ON

OFF

Output current

detection signal

(Y12)

Pr.166
Minimum 100ms
(initial value)

Output current

Pr.166 9999, Pr.167 = 0

Pr.151

OFF

ON

Start signal

Time

Output

current

OFF

ON

Zero current
detection time
(Y13)

Pr. 153
Detection time

Pr. 153
Detection time

Pr.152

OFF

ON

0[A]

100ms

*

Pr.152

* Once turned on, the zero current detection time

(Y13) signal is held on for at least 100ms.

Pr.

Selection of action conditions of
the second function signal (RT)

Pr.155 RT signal reflection time selection

Pr.155 Setting

Description

0 (initial value)

This function is immediately made valid with on
of the RT signal.

10

This function is valid only during the RT signal
is on and constant speed operation. (invalid
during acceleration/deceleration)

Function

First Function

Parameter Number

Second Function

Parameter Number

Torque boost

Pr.0

Pr.46

Base frequency

Pr.3

Pr.47

Acceleration time

Pr.7

Pr.44

Deceleration time

Pr.8

Pr.44, Pr.45

Electronic thermal O/L
relay

Pr.9

Pr.51

Stall prevention

Pr.22

Pr.48, Pr.49

156, 157

Refer to the section about Pr. 22 and

other relevant parameters.

158

Refer to the section about Pr. 54 and other

relevant parameters.

159

Refer to the section about Pr. 135 and other

relevant parameters.

Display of applied parameters and user group function

Pr.172 User group registered display/batch clear
Pr.173 User group registration

Pr.174 User group clear

Pr. 160

Setting

Description

9999

(initial

value)

Only the simple mode parameters can be displayed.

0

Simple mode+extended parameters can be displayed.

1

Only parameters registered to the user group can be displayed.

Pr.

155

Pr.

Pr.

Pr.

Pr.

160

Pr.

172 to 174

Pr.160 User group read selection