MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual
Page 26
27
867
AM output filter
0 to 5s
0.01s
0.01s
872
Input phase failure protection selection
0, 1
1
0
R
e
ge
ner
at
io
n
av
oi
da
nc
e f
unc
tion
882
Regeneration avoidance operation
selection
0, 1
1
0
883
Regeneration avoidance operation level
300 to 800V
0.1V
380V/760V
884
Regeneration avoidance at deceleration
detection sensitivity
0 to 5
1
0
885
Regeneration avoidance compensation
frequency limit value
0 to 10Hz, 9999
0.01Hz
6Hz
886
Regeneration avoidance voltage gain
0 to 200%
0.1%
100%
Fr
ee
par
am
e
te
r
888
Free parameter 1
0 to 9999
1
9999
889
Free parameter 2
0 to 9999
1
9999
En
er
gy
s
avi
n
g
m
oni
to
r
891
Cumulative power monitor digit shifted
times
0 to 4, 9999
1
9999
892
Load factor
30 to 150%
0.1%
100%
893
Energy saving monitor reference (motor
capacity)
0.1 to 55/0 to 3600kW
0.01/0.1kW
Inverter rated
capacity
894
Control selection during commercial
power-supply operation
0, 1, 2, 3
1
0
895
Power saving rate reference value
0, 1, 9999
1
9999
896
Power unit cost
0 to 500, 9999
0.01
9999
897
Power saving monitor average time
0, 1 to 1000h, 9999
1
9999
898
Power saving cumulative monitor clear
0, 1, 10, 9999
1
9999
899
Operation time rate (estimated value)
0 to 100%, 9999
0.1%
9999
Ca
lib
ra
tio
n
p
ara
me
te
rs
C0
(900)
FM terminal calibration
C1
(901)
AM terminal calibration
C2
(902)
Terminal 2 frequency setting bias
frequency
0 to 400Hz
0.01Hz
0Hz
C3
(902)
Terminal 2 frequency setting bias
0 to 300%
0.1%
0%
125
(903)
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
C4
(903)
Terminal 2 frequency setting gain
0 to 300%
0.1%
100%
C5
(904)
Terminal 4 frequency setting bias
frequency
0 to 400Hz
0.01Hz
0Hz
C6
(904)
Terminal 4 frequency setting bias
0 to 300%
0.1%
20%
126
(905)
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
C7
(905)
Terminal 4 frequency setting gain
0 to 300%
0.1%
100%
989
Parameter copy alarm release
10/100
1
10/100
-
PU
990
PU buzzer control
0, 1
1
1
991
PU contrast adjustment
0 to 63
1
58
Cle
a
r
pa
ra
m
et
er
s
Pr.CL
Parameter clear
0, 1
1
0
ALLC
All parameter clear
0, 1
1
0
Er.CL
Alarm history clear
0, 1
1
0
PCPY
Parameter copy
0, 1, 2, 3
1
0
*1
The initial value differs according to the voltage class. (200V class / 400V class)
*2
Differ according to capacities. (55K or less/75K or more)
Function
Parameters
Name
Setting Range
Increments
Initial Value
Refer to